Status LED indication

 

Standard models

 

Orange Power OK LED

 

 

Cyclic chargers

 

Three color LED, red-yellow-green

 

Isolations

 

Input - chassis

 

1500VAC

 

 

Input - output

 

3750VAC

 

 

Output - chassis

 

500VAC

 

Standards

 

Safety

 

EN60335-2-29 +A2

 

 

EMC

 

EN55022B, EN50081-1, EN50082-2

 

Approvals

 

 

CE marking

 

Protection class

 

Mechanical

 

IP20 metal enclosure

 

 

Electrical

 

Class I

 

Connectors

 

Input 
Output

 

Input power cord 
10 m

2  

2m output cables

 

Dimensions

 

l x w x h

 

267 x 135 x 85 mm with rubber ends

 

Weight

 

 

1,9kg without output cables

 

Mounting

 

 

Wall, bench

 

Cooling

 

 

Temperature controlled fan

 

Operating temperature range

 

Full power typically

 

-25ºC...+40ºC

 

 

Reduced power

 

+40…+ 70ºC, see curve below

 

Humidity

 

 

0…95%, non condensing

 

 

DATASHEET / OPERATING INSTRUCTIONS

 

 

 

TECHNICAL DATA 

 

Input voltage 

50…260 VAC (50…200VAC reduced power, see curve below) 

50…340 VDC (50…200VDC reduced power) 

Input current 

9 A 

Power factor 

>0.99 

Efficiency (230VAC, 10…100% load) 

> 88% 

Inrush current 

<30A, cold start 

Line regulation 

0.01% 

Load regulation 

0.2V 

Output setting accuracy 

± 0.1% 

Output ripple (f > 50Hz) 

<30mVrms 

Hold up time 

> 5ms 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Nominal output voltage / current characteristics 1600W models 

 
 

 

 

 

 

 

 

Output power / input voltage derating curve 

Output power and fan speed vs ambient temperature 

 
 
 
 
 

Summary of Contents for ZAT1600 SERIES

Page 1: ...600W Power Supplies and Battery Chargers ZAT1600 SERIES TASHEET OPERATING INSTRUCTIONS Wide output adjustment range 0 72VDC Analog control by external 0 5VDC voltage Temp comp charging sense as on option Power fail relay alarm Master Slave connection Analog control modular connector Microprocessor controlled charging curves for all kind of batteries Master Slave connection ...

Page 2: ... see table Output current see table Max power Installation dimensions Width x Height x Depth mm ZAT1600 27 4 60 T 55 264VAC 78 340VDC 27 4 VDC 5 36VDC 60 A 1600W Wall Bench 267x135x85 ZAT1600 41 1 45 T 55 264VAC 78 340VDC 41 1 VDC 12 54VDC 40 A 1600W Wall Bench 267x135x85 ZAT1600 54 8 30 T 55 264VAC 78 340VDC 54 8 VDC 24 72VDC 30 A 1600W Wall Bench 267x135x85 Cable sets with modular connectors are...

Page 3: ...sions l x w x h 267 x 135 x 85 mm with rubber ends Weight 1 9kg without output cables Mounting Wall bench Cooling Temperature controlled fan Operating temperature range Full power typically 25ºC 40ºC Reduced power 40 70ºC see curve below Humidity 0 95 non condensing DATASHEET OPERATING INSTRUCTIONS TECHNICAL DATA Input voltage 50 260 VAC 50 200VAC reduced power see curve below 50 340 VDC 50 200VDC...

Page 4: ...nstant orange light To avoid sparking turn the power off before disconnecting the cables CONNECTION WITH DC INPUT Wires in PSU s power cable to be connected as follows L DC input positive or negative N DC input negative or positive PE Ground OUTPUT VOLTAGE AND CURRENT LIMIT ADJUSTMENT Trimmer or analog control adjustable modules type example ZAT1600 24 60 or ZAT1600 24 60 AI The output voltage and...

Page 5: ... code Switch N N PIN CONFIGURATION MODULAR CONNECTORS Front panel Rear panel J1 Analog input 0 5VDC J3 Temperature compensation Sense option J5 RS 232 bus in and out master slave Alternatively power fail relay alarm OPTIONAL ALARM RELAY If the unit is ordered with alarm relay for example ZAT1600 24 60 H the potential free alarm output indicates if the charger s output is healthy The alarm signal i...

Page 6: ...output terminals That allows serial and parallel connection to separate power supply s so that equal steering voltages are used Number or connected devices are not limited Only be sure that 500V insulation voltage is not exceeded Connection example using internal 5VDC power source and external potentiometers 5V output can be used to feed logic voltages for external circuits Connection in an exampl...

Page 7: ...le If more current is needed adjustable Master power supply can be parallel or series connected via digital bus to Slave power supply which equals Master but is without adjustment possibility Then output current or voltage is doubled and the both supplies can still be adjusted thought multi turn potentiometers Max one slave unit can be used in master slave connection as a standard Please contact y...

Page 8: ...rrent 5 5 0 12 VDC 11 4 VDC 12 6 VDC 45 A 1 12 VDC 13 7 VDC 13 VDC 14 39 VDC 45 A 2 15 VDC 14 3 VDC 15 75 VDC 45 A 3 20 VDC 19 VDC 21 VDC 45 A 4 24 VDC 22 8 VDC 25 2 VDC 45 A 5 24 VDC 27 4 VDC 26 VDC 28 77 VDC 45 A 6 30 VDC 28 5 VDC 31 5 VDC 45 A 7 33 VDC 31 4 VDC 34 65 VDC 45 A 8 36 VDC 34 2 VDC 37 8 VDC 45 A 9 38 VDC 36 1 VDC 39 9 VDC 45 A A 36 VDC 41 1 VDC 39 VDC 43 16 VDC see curve B 36 VDC 41...

Page 9: ...ut cables of the charger output short circuit Connect the charger to the power line Follow the Status led color Switch ON the charger from the on off switch Count all the number of green blinks There must be as much number of blinks as the code switch position number is Note If the position of the code switch is O Status led blinks only once and returns to red The code switch positions A F respond...

Page 10: ...e The output voltage can be tuned 5 from its nominal value Choose such programmed output voltage which can reach the desired voltage by 5 adjustment Read the instruction from Changing programmed voltage Connect the voltage meter to output wires Tune with a small screw driver the voltage calibration trimmer and check the result from volt meter Clockwise direction increases the voltage Look at the p...