Precise control:
when selecting this option ("Yes"), the 1-byte object "A/C Unit - Fan
precise" appears, which allows eatablishing the value, in percentage, of the desired fan speed
level, according to the values shown in Table 3.1.
Step control and Precise control can be jointly enabled, so that the fan speed can be controlled any
time in one manner or other, as desired.
2.6. TEMPERATURE
From this window it is possible to configure several parameters related to the setpoint
temperature sent to the A/C Unit.
Note that the parameters shown below do not apply in modes
“Fan” and “Dry” (in those cases, the
general setpoint is calculated as in mode “Cool”, but without taking the restrictions into account).
Figure 3.5. Temperature window
Temperature range (only for Heat and Cool modes):
it is possible to define limits for
the setpoint temperature sent to the machine of each mode:
Cool mode Min. Temperature:
establishes the minimum general setpoint
temperature, in ºC, allowed for the Cool mode. This value must be in the range 16-30ºC.
Heat mode Max. Temperature:
establishes the maximum setpoint temperature, in
ºC, allowed for the Heat mode. This value must be in the range 16-30ºC.