                  RailQUAD 8 

http://www.zennio.com

  

 

   

                       

Technical Support:

 http://support.zennio.com 

 

12 

164, 194, 224

 

2 Bytes

 

I

 

C - - W -

 

DPT_Value_Temp

 

-273.00º - 670760.00º

 

[Tx] Basic Setpoint

 

Reference Setpoint

 

15, 45, 75, 105, 135, 

165, 195, 225

 

1 Bit

 

I

 

C - - W -

 

DPT_Step

 

0/1

 

[Tx] Setpoint Step

 

0 = -0.5ºC; 1 = +0.5ºC

 

16, 46, 76, 106, 136, 

166, 196, 226

 

2 Bytes

 

I

 

C - - W -

 

DPT_Value_Tempd

 

-670760.00º - 

670760.00º

 

[Tx] Setpoint Offset

 

Float Offset Value

 

17, 47, 77, 107, 137, 

167, 197, 227

 

2 Bytes

 

O

 

C T R - -

 

DPT_Value_Temp

 

-273.00º - 670760.00º

 

[Tx] Setpoint Status

 

Current Setpoint

 

18, 48, 78, 108, 138, 

168, 198, 228

 

2 Bytes

 

O

 

C T R - -

 

DPT_Value_Temp

 

-273.00º - 670760.00º

 

[Tx] Basic Setpoint Status

 

Current Basic Setpoint

 

19, 49, 79, 109, 139, 

169, 199, 229

 

2 Bytes

 

O

 

C T R - -

 

DPT_Value_Tempd

 

-670760.00º - 

670760.00º

 

[Tx] Setpoint Offset Status

 

Current Setpoint Offset

 

20, 50, 80, 110, 140, 

170, 200, 230

 

1 Bit

 

I

 

C - - W -

 

DPT_Reset

 

0/1

 

[Tx] Setpoint Reset

 

Reset Setpoint to Default

 

1 Bit

 

I

 

C - - W -

 

DPT_Reset

 

0/1

 

[Tx] Offset Reset

 

Reset offset

 

21, 51, 81, 111, 141, 

171, 201, 231

 

1 Bit

 

I

 

C - - W -

 

DPT_Heat_Cool

 

0/1

 

[Tx] Mode

 

0 = Cool; 1 = Heat

 

22, 52, 82, 112, 142, 

172, 202, 232

 

1 Bit

 

O

 

C T R - -

 

DPT_Heat_Cool

 

0/1

 

[Tx] Mode Status

 

0 = Cool; 1 = Heat

 

23, 53, 83, 113, 143, 

173, 203, 233

 

1 Bit

 

I

 

C - - W -

 

DPT_Switch

 

0/1

 

[Tx] On/Off

 

0 = Off; 1 = On

 

24, 54, 84, 114, 144, 

174, 204, 234

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] On/Off Status

 

0 = Off; 1 = On

 

25, 55, 85, 115, 145, 

175, 205, 235

 

1 Byte

 

O

 

C T R - -

 

DPT_Scaling

 

0% - 100%

 

[Tx] Control Variable (Cool)

 

PI Control (Continuous)

 

26, 56, 86, 116, 146, 

176, 206, 236

 

1 Byte

 

O

 

C T R - -

 

DPT_Scaling

 

0% - 100%

 

[Tx] Control Variable (Heat)

 

PI Control (Continuous)

 

27, 57, 87, 117, 147, 

177, 207, 237

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Control Variable (Cool)

 

2-Point Control

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Control Variable (Cool)

 

PI Control (PWM)

 

28, 58, 88, 118, 148, 

178, 208, 238

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Control Variable (Heat)

 

2-Point Control

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Control Variable (Heat)

 

PI Control (PWM)

 

29, 59, 89, 119, 149, 

179, 209, 239

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Additional Cool

 

Temp >= (SBand) => "1"

 

30, 60, 90, 120, 150, 

180, 210, 240

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] Additional Heat

 

Temp <= (Setpoint-Band) => "1"

 

31, 61, 91, 121, 151, 

181, 211, 241

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] PI State (Cool)

 

0 = PI signal 0%; 1 = PI signal greater than 0%

 

32, 62, 92, 122, 152, 

182, 212, 242

 

1 Bit

 

O

 

C T R - -

 

DPT_Switch

 

0/1

 

[Tx] PI State (Heat)

 

0 = PI signal 0%; 1 = PI signal greater than 0%

 

243, 247, 251, 255, 

259, 263, 267, 271

 

2 Bytes

 

O

 

C T R - -

 

DPT_Value_Temp

 

-273.00º - 670760.00º

 

[Ix] Current Temperature

 

Temperature sensor value

 

244, 248, 252, 256, 

1 Bit

 

O

 

C T R - -

 

DPT_Alarm

 

0/1

 

[Ix] Overcooling

 

0 = No Alarm; 1 = Alarm

 

Summary of Contents for RailQUAD 8

Page 1: ...RailQUAD 8 Analogue Digital Multifunction Input Module for DIN rail ZIO RQUAD8 USER MANUAL Application program version 1 3 1 4 User manual edition 1 4 _a www zennio com...

Page 2: ...o com 2 CONTENTS Contents 2 Document Updates 3 1 Introduction 4 1 1 RailQUAD 8 4 1 2 Installation 5 2 Configuration 7 2 1 General 7 2 2 Inputs 8 2 2 1 Binary Input 9 2 2 2 Temperature Probe 9 2 2 3 Mo...

Page 3: ...anges in the application program Optimisation of inputs thermostat and heartbeat modules Minor text changes 1 2 _a Changes in the application program Optimisation of the binary inputs motion detector...

Page 4: ...dels provided by Zennio or other NTC temperature probes from other suppliers being in that case possible to configure their parameters in ETS Motion detector Moreover RailQUAD 8 implements 8 independe...

Page 5: ...ted LED 4 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode In such case the LED will blink in red every 0 5 seconds Inputs 1 3 i...

Page 6: ...io com 6 To obtain further information about the technical features of RailQUAD 8 and on security and installation procedures please refer to the Datasheet of the device bundled with the original pack...

Page 7: ...ATION The only parameterisable screen available by default is General From this screen it is possible to activate deactivate all the required functionality Figure 2 General Heartbeat Periodic Alive No...

Page 8: ...uired it can be left as Disabled Thermostat x enabled disabled enables or disables thermostat number x One entry per input or thermostat will be included into the tab tree on the left 2 2 INPUTS RailQ...

Page 9: ...as the light level Depending on the detection different response actions can be parameterised Please refer to the Motion Detector user manual available under the RailQUAD 8 product section at the Zenn...

Page 10: ...g up to eight thermostat functions with independence of the number of the inputs that have been configured Please refer to the specific Zennio Thermostat user manual available under the RailQUAD 8 pro...

Page 11: ...Standby 3 Economy 4 Building Protection Tx Special Mode 1 byte HVAC Mode 7 37 67 97 127 157 187 217 1 Bit I C W DPT_Ack 0 1 Tx Special Mode Comfort 0 Nothing 1 Trigger 1 Bit I C W DPT_Switch 0 1 Tx Sp...

Page 12: ...DPT_Switch 0 1 Tx On Off 0 Off 1 On 24 54 84 114 144 174 204 234 1 Bit O C T R DPT_Switch 0 1 Tx On Off Status 0 Off 1 On 25 55 85 115 145 175 205 235 1 Byte O C T R DPT_Scaling 0 100 Tx Control Varia...

Page 13: ...Up 1 Bit C T DPT_UpDown 0 1 Ix Short Press Move Down Shutter Sending of 1 Down 1 Bit C T DPT_UpDown 0 1 Ix Short Press Move Up Down Shutter Switching 0 1 Up Down 1 Bit C T DPT_Step 0 1 Ix Short Press...

Page 14: ...T DPT_Value_2_Ucount 0 65535 Ix Short Press Constant Value Integer 0 65535 2 Bytes C T 9 xxx 671088 64 670760 96 Ix Short Press Constant Value Float Float Value 277 283 289 295 301 307 313 319 1 Byte...

Page 15: ...1 Bit C T DPT_Switch 0 1 Ix Long Press Light Off Sending of 0 Off 1 Bit I C T W DPT_Switch 0 1 Ix Long Press Light On Off Switching 0 1 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Long Press Run Scene...

Page 16: ...388 417 446 475 504 533 1 Bit O C T R DPT_Occupancy 0 1 Ix Presence State Binary Binary Value 1 Bit O C T R DPT_Ack 0 1 Ix Presence Slave Output 1 Motion Detected 331 360 389 418 447 476 505 534 1 Bi...

Page 17: ...Building Protection 341 346 351 370 375 380 399 404 409 428 433 438 457 462 467 486 491 496 515 520 525 544 549 554 1 Bit O C T R DPT_Switch 0 1 Ix Cy Detection State Binary Binary Value 342 347 352...

Page 18: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Reviews: