Once IRSC is connected and properly parameterised, it will be possible to control the
A/C unit from within the installation (for instance, from the InZennio Z38i or InZennio
Z41 touch panels), thus achieving an easier and more intuitive control.
Note
:
only one air conditioning unit may be controlled by each IRSC.
To obtain detailed information about the technical features of IRSC, as well as on
security and installation procedures, please refer to the device Datasheet, provided
with the original packaging of the device and also available at
http://www.zennio.com
.
1.3
THE IRSC ZONE APPLICATION PROGRAM
The
IRSC Zone
application program has been developed for controlling
air
cooling/heating ducted machines
, thus allowing acclimatizing, within the same KNX
installation, up to 8 rooms (or zones) where the air output is regulated by gates or
motorised grilles
. Grilles are the final elements of the air ducts in charge of
distributing the air from the central unit to every zone, and permit outputting the
conditioned air to the different zones.
IRSC Zone is therefore in charge of two complementary functions:
Sending the necessary orders (ON/OFF, temperature, fan, etc) to the
central
a/c machine
through infrared commands.
Sending the necessary orders to the external KNX actuator that controls the
air grilles
.
The independent control of these grilles makes it possible, in short, that a sole machine
with a unique setpoint temperature serves each of the zones as convenient, no matter
if the setpoint temperatures of the zones are different.
The central machine is controlled by taking into account the number of the zones to be
acclimatised, as well as their own setpoints:
The IRSC Zone application program calculates the setpoint temperature that
the central machine needs to be sent depending on what the desired
temperatures for the different zones are.