Figure 8. Temperature window
Temperature range (only for Heat and Cool modes)
:
it is possible to define
limits for the setpoint temperature sent to the machine of each mode:
Cool mode min. temperature
:
establishes the minimum general setpoint
temperature, in ºC, allowed for the Cool mode. This value must be in the
range 16-30ºC.
Heat mode max. temperature
: establishes the maximum setpoint
temperature, in ºC, allowed for the Heat mode. This value must be in the
range 16-30ºC.
Once this option has been enabled, the “Temperature restriction” 1-bit object
becomes available, with value “1” by default. Temperatures will be subject to
the above limits only while the value of this object is "1". The value “0”, on the
other hand, means that the parameterised restriction should be escaped.
If a setpoint over the maximum limit or under the minimum level is calculated
while the temperature restriction is active, the setpoint value effectively sent
to the A/C unit will become truncated to the corresponding limit.
Note
:
the setpoint temperature sent to the machine may exceed the
parameterised restrictions (even if the “Temperature restriction” object has
the value “1”) in the case of having parameterised a calibration (parameter
“Increase (heat) / Decrease (cool) temperature sent to the A/C unit by”,
explained below) or if the “Temperature returned from external sensor”
parameter, explained next, is enabled.