Sending of grille statuses
: sets if grille status objects ("Zone x - Grille
status reception") should be sent to the bus in addition to the machine
status objects after a bus power failure, a device reset from ETS or a
download.
Delay
: time, in seconds, that IRSC will wait before proceeding with this
sending.
Sending status to A/C unit on bus voltage recovery
: allows choosing
whether to send or not the current status values to the A/C unit (i.e., through
infrared commands) after a bus power failure, a device reset from ETS or a
download.
Delay:
time, in seconds, that IRSC will wait before proceeding with this
sending.
Related to device reboots, there is also the option to make IRSC Zone send read
requests to the bus in order to get updated values of the objects that determine the
initial state it should assume when it becomes functional. Such option (
Zone update
on start-up
) has been described in section 3.2.
Note
:
when initial sendings are enabled from the Reset window having already enabled
the “Zone update on start-up” parameter from the General as well, special attention
must be paid while setting the
delays
of both parameters. Since the purpose of
enabling the latter is that IRSC Zone requests state information from the KNX
environment, it would not make sense that, prior to this, IRSC Zone had already sent
information to the KNX bus, as this may overwrite the actual state values of the
installation with the default values the device acquires after a download or an ETS
reset. Because of this, the delays in the Reset window should be greater than that
parameterised for the “Zone update on start-up” parameter.