inBOX 24 vT / inBOX 20 vT
Technical Support:
8
Sending of Indication Objects (0 and 1) on Bus Voltage Recovery
: this
parameter lets the integrator activate
two new communication objects (“
Reset
0
” and “
Reset 1
”), which will be sent to the KNX bus with values “0” and “1”
respectively whenever the device begins operation (for example, after a bus
power failure). It is possible to parameterise a certain
delay
to this sending (0
to 255 seconds).
Figure 3.
Sending of Indication objects on bus voltage recovery
Heartbeat (Periodical Alive Notification)
: this parameter lets the integrator
incorporate a one-bit object
to the project (“
[Heartbeat] Object to Send ‘1’
”)
that will be sent periodically
with value “1” to notify that the device is still
working (
still alive
).
Figure 4
. Heartbeat (Periodical Alive Notification).
Note
:
The first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following sendings match
the period set
.
Show Relay Switches Counter Objects
[
disabled
/enabled
]: (only on inBOX
20 vT) enables two communication objects to keep track of the number of
switches performed by each of the relays ("
[Relay X] Number of Switches
")
and the maximum number of switches carried out in a minute ("
[Relay X]
Maximum Switches per Minute
").