DALIBOX Interface 64/32
Technical Support:
48
options are analogous to those for locking, but will also comprise the following
one: “Previous State” (to recover the status previous to the lock order).
2.5.9
CUSTOM INITIALISATION
This function lets customising the state of the group after the start-up of the device.
Opting for the
default initial configuration
implies the following:
After an ETS download, the ballasts of the group will remain off.
After recovering from a KNX bus power failure, the ballasts of the group will
recover their state previous to the power failure.
On the other hand, opting for a
custom initial configuration
allows parameterising the
desired state after the bus power is restored or after a download.
Note
:
KNX bus failures do not switch off the ballasts, unless their own power supply is
interrupted.
ETS PARAMETERISATION
Once the option to customise the initial configuration has been enabled (otherwise, the
default configuration will be applied) the following parameters will show in ETS:
Figure 23.
Custom initialisation