DALIBOX Interface 64/32
Technical Support:
46
2.5.7.2
FLASHING
The flashing function requires configuring the following options:
On Duration
: length of each “On” stage during the sequence.
Off Duration
: length of each “Off” stage during the sequence.
Repetitions
: number of iterations of the sequence.
On Value
: dimming level to be a
pplied to the group during the “On” stages.
Final Value
: dimming level to be applied to the group after the last repetition
or after the reception.
PARAMETRIZACIÓN ETS
Once the flashing function has been enabled, the “
[Group n] Flashing
” one-bit object
will turn visible in order to let triggering an On-Off-
On… sequence by sending it the value
“1”, as well as interrupting it by sending it the value “0” The options for this function are
the following:
Figure 21.
Flashing
On Duration
[
1
…255
] [
s
/min
]:
sets the length of each “On” stage.
Off Duration
[
1
…255
] [
s
/min
]:
sets the length of each “Off” stage.
Repetitions
[
0
…100
]: sets the number of iterations of the sequence. A value
of
“0” (default option) causes an endless repetition, until an order to interrupt
the sequence is received.