DALIBOX Interface 64/32
Technical Support:
43
2.5.7.1
SIMPLE TIMER
The simple timer function requires configuring the following options:
On Duration
: time the group must remain on before being automatically
switched off (unless the stop order is received from the bus, which will switch
the group off immediately).
On Delay
: delay between the reception of the simple timer trigger order and
the actual switch-on of the group.
Off Delay
: delay between the reception of the simple timer stop order and the
actual switch-off of the group.
Action in Case of Retriggering
: action to be performed in case the simple
value trigger order is received several times.
➢
Nothing
: the current time count will not be restarted.
➢
Restart
: the time count of the On Duration will be restarted from zero.
➢
Multiply
: the time count of the On Duration will become ‘n’ times the
configured time, being ‘n’ the number of times the value “1” is received (up
to 5 times).
On Value
: dimming level to
be applied to the group during the “on” stage.
Dimming Time
: desired regulation type for the transitions.
Note
:
the simple timer function will be interrupted whenever any other dimming action is
commanded, no matter if it falls within the On Duration or during the On/Off delays.
ETS PARAMETERISATION
Once
the simple timer function has been enabled, the “
[Group n] Simple Timer
” one-
bit object becomes enabled too, making it possible to trigger a switch-on by sending it
the value “1” or a switch-off by sending it the value “0”. Both actions can be delayed
according to the following parameters: