Putting into use
■
Open valves carefully and check installation for
leakage.
■
If the sleep mode of the counter is enabled
(Display:
SLEEP 1
), then it must be deactivat-
ed by longer pressing the button (>5s).
■
While the system is operating, check whether
the volume display advances and the tem-
peratures displayed correspond with the actual
temperatures (see the display overview).
■
Wait for the temperature display to be updated
(1-2 sec).
■
Secure meter with the enclosed sealing mate-
rial against unauthorised removal.
■
Fill in the putting into use report in accordance
with PTB-Directive TR K9.
Consumer
Asymmetrical sensor installation for zelsius
®
C5-ISF with the return
sensor integrated in the flow sensor
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-ISF
Supply
Return
Consumer
Asymmetrical sensor installation for zelsius
®
C5-ISF with the return
sensor integrated in the flow sensor
Supply
Return
Consumer
Symmetrical sensor installation for zelsius
®
C5-ISF
Supply
Return
Note relating to the mounting in existing im-
mersion sleeves:
The device C5 can be put into use in connection
with existing immersion sleeves in accordance
with the article “Putting into use of MID homolo-
gated temperature sensors” released in the PTB
notifications 119 (2009), vol.6.
Based on current information, the regulation has
a period of validity until 30.10.2016. For the iden-
tification
and marking of the usable existing immersion
sleeves in connection with the C5 device, an
identification and marking set can be delivered
from our company.