Holding Registers (write)
Address Holding Register ID
Minimum
Maximum
Scaling
Units
0
COMMS_REF
-100.0
100.0
x
10
%
1
F100 PRESET 1
-100.0
100.0
x
10
%
2
C030 ACCEL TIME
0.5
600.0
x
10
sec
3
C031 DECEL TIME
0.5
600.0
x
10
sec
4
C032 S TIME
0.01
40.00
x
10
sec
5
D01 CURRENT LIM
22% of model
current rating
125% of model
current rating
x
10
A
6
E030 ARs ALLOWED
0
15
7
E031 AR CLR TIME
0
1200
8
G050 UNDER SPEED
-100.0
100.0
x
10
%
9
G051 OVER SPEED
-100.0
100.0
x
10
%
The "Scaling" instruction of this table will convert a decimal value in the given units to a raw signed 16
bit integer.
Function Codes
• Function Code 01: Read Coils
• Function Code 02: Read Discrete Inputs
• Function Code 03: Read Holding Registers
• Function Code 04: Read Input Registers
• Function Code 05: Write Single Coil
• Function Code 06: Write Single Register
• Function Code 07: Read Exception Status
• Function Code 08: Diagnostics, Sub Codes 0,2,10…18,20
• Function Code 15: Write Multiple Coils
• Function Code 16: Write Multiple Holding Registers
• Function code 43: Read device Identification, Sub Code 14
The function codes supported are explained in detail in the document entitled “MODBUS Application
Protocol Specification V1.1b”. Available from http://www.modbus.org. Implementation options and
constraints of the MSC-3 are explained in the following sections.