IM00120
88
IM00120
MSC-3 Start Up
F09 COMMS PRESET
F09 COMMS PRESET
60.0%
Range: -100.0...100.0 % of
C03 MAX Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.
The
F09 COMMS PRESET
parameter is the power-on value for the >
COMMS REF
reference. The
> COMMS REF
is the reference by the operating communication network protocol.In the event that
communications is lost, the COMMS REF reference will automatically revert to the
F09 COMMS
PRESET
parameter value. See
G168 Comms Lost Time
on page 112 for further details. Setting
G168
Comms Lost Time
to zero disables the detection of communications loss.
F10 PRESETS
There are 8 preset references for the MSC-3. Most are used in conjunction with the Reference Selector.
Each preset is expressed as a percentage of
C03 MAX Hz
.
F100 PRESET1 to F107 PRESET8
F100 PRESET 1
10.0%
F104 PRESET 5
50.0%
F101 PRESET 2
20.0%
F105 PRESET 6
60.0%
F102 PRESET 3
30.0%
F106 PRESET 7
70.0%
F103 PRESET 4
40.0%
F107 PRESET 8
80.0%
Range: -100.0...100.0 % of C03 MAX Hz
• Press
to edit the value.
• Press
▲
/
▼
to make changes to the value.
• Press
to accept the new value OR
• Press
ESC
to abandon the value change.