55
Pressure Sensor Zero
In order to make sure the pressure measure work correctly, the zero point of
the pressure sensor must be checked regularly and reset if necessary.
Resetting is necessary:
■
If the quantity deviates by more than 20mBar from the target value
■
If the Air-Con Service Station has been shaken, for exampleduring
transport on bumpy roads
■
Every four to six weeks
1.In standby mode, press
button , use the
or
button to
select “
PRESSURE SENSOR ZERO
” item