background image

26

Maintenance

General

Each unit on a project will 
have its own unique operating 
environment and conditions 
which dictate a maintenance 
schedule for that unit that 
may be different from other 
equipment on the project. A 
formal regular maintenance 
schedule and an individual 
unit log should be established 
and maintained. Following this 
schedule will help maximize the 
performance and service life of 
each unit on the project.

The safety considerations listed 
in the front of this manual should 
be followed during any service 
and maintenance operations.

For more detailed service 
information consult your Sales 
Representative or the factory.

Disconnect power supply from 
the unit before servicing.

Filter

Since the Vertical Hi-Stack 
Fan Coil is a draw-through coil 
type, filter must be changed 
or cleaned a minimum of four 
times a year. Under certain 
operating conditions, it may be 
necessary to change or clean the 
filters more frequently to obtain 
maximum unit performance. 

Coil

Coils may be cleaned by 
removing the motor/blower 
assembly and air filter, providing 
access to the air entry side of 
the coil. Brush the entire finned 
surface with a soft bristled 
brush, brushing parallel to the 
fins, taking care not to damage 
the fins. Brushing should be 
followed by cleaning with a 

vacuum cleaner. Compressed air can 
also be used by blowing air through 
the coil fins from the leaving air side, 
again followed by vacuuming. If fins 
are damaged during the cleaning 
process, a 12 fins per inch fin comb 
can be used to straighten the fins. 
 
For a deeper cleaning, spray the 
finned surface with a neutral cleaning 
solution and rinse thoroughly. 
Zehnder Rittling recommends using 
neutral pH cleaners. Avoid the use 
of strong acids and strong base 
cleaners. Thus, cleaners with pH 
range from 5 to 11 are suitable for coil 
cleaning. This range includes such 
over-the-counter cleaners as Simple 
Green

® 

All Purpose Cleaner, or HVAC 

coil cleaners like Nu-Calgon Evap 
Pow'r

®. 

Strong acidic cleaners (pH of 

5 or less) that contain hydrochloric, 
sulfuric, nitric or acetic acid are 
not recommended for use on 
copper-tube, aluminum fin coils. 
Presence of these acids will result 
in rapid corrosion of the metals. 
Strong alkali (base) cleaners (pH 
of 11 or more) containing sodium, 
potassium or ammonium hydroxide 
are not recommended as they will 
aggressively corrode aluminum 
tubes and fins. Strong ammonium 
hydroxide cleaners will also cause 
stress corrosion cracking of copper 
tubes. Zehnder Rittling recommends 
completely rinsing all cleaners from 
the coil, including cleaners identified 
as no-rinse cleaners. Residual 
cleaners may decompose over time 
producing low molecular weight, 
organic acids that lead to formicary 
corrosion.

Failure to maintain a clean coil 
surface will result in reduced airflow, 
reduced performance and increased 
power consumption. Clean the coil at 
every inspection. Units provided with 
the proper type of air filters, replaced 
regularly, will require less frequent 
coil cleaning.  Before performing 
service at or near any heating coil, 

piping or valve, disconnect all 
power, close all isolation valves 
and allow the equipment to cool. 

Drain

Once yearly, preferably at the 
start of the cooling season, the 
drain pan should be checked and 
cleaned if necessary. A flexible 
probe for 3/4-inch pipe may be 
used to clear any obstruction 
from the line, or the drain tube 
may be removed through the 
lower area of the return-air 
opening, should more thorough 
cleaning be needed. 

Motor/blower assembly

The type of fan operation is 
determined by the control 
components and their method of 
wiring. This may vary from unit to 
unit. Refer to the wiring diagram 
located in a zip-lock plastic bag 
on the air block-off plate of each 
unit for that unit’s individual 
operating characteristics. 
 
All motors have permanently 
lubricated bearings so no further 
field lubrication is ever required. 
 
The unit motor/blower is direct-
drive assembly. Remove the air 
block-off plate to gain access to 
the motor/blower assembly. The 
entire motor/blower assembly 
can be removed from its track 
through the return-air grille 
for field servicing by removing 
a single screw and quick 
connect. Disconnect all remote 
electric power supplies before 
servicing as motors can start 
automatically.  
Dirt and dust should not be 
allowed to accumulate on the 
blower wheel or housing. Failure 
to keep this clean may result in 
an unbalanced wheel condition 
which can lead to a damaged 
blower wheel or motor. The wheel 
and housing may be cleaned 

Summary of Contents for FVH series

Page 1: ...i Cooling Fresh Air Clean Air Heating Vertical Hi Stack Fan Coil Installation Operation and Maintenance...

Page 2: ...k connections 16 Wiring diagram 17 Electrical connections 19 Enclosing unit 20 Start up 22 Water systems 23 EC Motor 25 Control operations 25 Maintenance 26 Replacement parts 28 Troubleshooting 29 Equ...

Page 3: ...shown in diagrams to the right Outside air available on left or right side of unit opposite riser side Available on both sides with back riser location Optional riser chase available for hideaway unit...

Page 4: ...78 6 Heating capacity optional 1 row reheat coil MBH 19 9 23 7 31 6 38 6 48 6 52 0 GPM 2 1 2 4 3 2 4 0 4 9 5 3 PD ft of H2 O 7 5 10 3 17 3 7 1 10 9 12 3 Heating capacity optional 2 row reheat coil MB...

Page 5: ...ulation Condensate insulation 2 1 2 1 2 3 4 1 2 2 1 2 1 1 2 2 1 2 1 1 2 1 2 1 1 2 3 4 3 4 1 2 1 1 4 3 4 1 1 2 1 3 4 1 1 4 1 2 1 1 4 3 4 3 4 3 4 1 3 4 1 3 4 Notes All dimensions are in inches All dimen...

Page 6: ...by others in field Risers available from 3 4 to 2 1 2 diameter with 1 2 or 3 4 thick insulation Riser length is 104 115 standard Back riser location shown See arrangement drawings for available unit c...

Page 7: ...del FVS slave Notes All dimensions are in inches All dimensions are 1 4 Wiring from electrical entry point to control enclosure is furnished and installed by others in field Outside air damper opening...

Page 8: ...ceptable riser combinations Supply Return Insulation Condensate Insulation 2 1 2 1 2 3 4 1 2 2 1 2 1 1 2 2 1 2 1 1 2 1 2 1 1 2 3 4 3 4 1 2 1 1 4 3 4 1 1 2 1 3 4 1 1 4 1 2 1 1 4 3 4 3 4 3 4 1 3 4 1 3 4...

Page 9: ...notice Dimensional data Grille size A B C D 14 x 16 17 11 16 15 11 16 15 11 16 13 11 16 12 x 14 15 11 16 13 11 16 13 11 16 11 11 16 7 x 16 17 11 16 15 11 16 8 11 16 6 11 16 6 x 14 15 11 16 13 11 16 7...

Page 10: ...untersunk screw holes Standard finish is powder coated and will be the same color as the return grille Mounting hardware included All listed dimensions are approximate and are subject to change withou...

Page 11: ...eturn air grille Notes Frame and return grilles are shipped loose for field installation Optional grille does not come with a frame Contact the factory regarding extended front panels for additional c...

Page 12: ...drilling cutting or working with chemicals Never pressurize equipment beyond specified pressures as shown on unit rating plate Always pressure test with an inert fluid such as water or dry nitrogen to...

Page 13: ...for personal injury or property damage resulting from improper or unsafe practices during the handling installation service or operation of the equipment The installation of fan coils and all associat...

Page 14: ...he customer to provide the protection necessary to prevent vandalism and weather deterioration of the equipment Under no condition should the units be left unprotected from the elements The equipment...

Page 15: ...As the unit is righted align the risers with the unit below In the case of shipped loose risers install from the lowest floor to the highest floor After the risers are field tested for leaks the Fan C...

Page 16: ...inside the unit so condensate if formed will run back into the condensate pan and not out toward the riser Any water damage caused by not following this procedure is not covered under the warranty Mak...

Page 17: ...lowing this procedure is not covered under the warranty The riser connection joints should be hydrostatically tested for leaks before furring in the unit Pressure of water column alone is approximatel...

Page 18: ...tment Such recommendations will be made by the factory upon request All ductwork and or supply and return grilles should be installed in accordance with the project plans and specifications If not inc...

Page 19: ...ED FACTORY WIRED 18AWG FACTORY WIRED 12AWG Wiring diagram 120V Standard blower motor wiring chart Size High Medium Low Capacitor Capacitor size 03 Red Blue Black Gray Yel 5 F 04 Blue Black Brown Gray...

Page 20: ...ture sensor is used wire to thermostat tb1 terminals 1 and 2 High static blower motor wiring chart Size High Medium Low Capacitor Capacitor size 03 Blue Black Brown Gray Yel 1 5 F 04 Red Blue Black Gr...

Page 21: ...trical Code and any applicable local codes Branch circuit fusing and electrical disconnect means if required must be furnished and installed by others All unit mounted control components and electrica...

Page 22: ...When cutting out supply and return holes for grilles be sure to clean all drywall dust from coils drain pans and blower discharge plenum After drywall is in place and rooms are prepared for final wal...

Page 23: ...l and stud mounting lines Install drywall to sides of unit with optional cut outs for supply outside air and thermostat Install drywall to face of unit with optional cut outs for supply return and the...

Page 24: ...acturer s warranty Start up Before beginning any start up the start up personnel should take the time to familiarize themselves with the unit options accessories and control sequence to fully understa...

Page 25: ...not release air trapped in other parts of the system Inspect the entire system for potential air traps and independently vent those areas as required In addition some systems may require repeated vent...

Page 26: ...Before and during water system balancing conditions may exist due to incorrect system pressures which may result in noticeable water noise or undesired valve operation After the entire system is balan...

Page 27: ...tentiometers marked as FL01 FL02 FL03 to adjust the airflow associated with each input Each output can be adjusted from 0 to 100 of the motor s factory programmed operating range using an instrument s...

Page 28: ...l result in rapid corrosion of the metals Strong alkali base cleaners pH of 11 or more containing sodium potassium or ammonium hydroxide are not recommended as they will aggressively corrode aluminum...

Page 29: ...lement will also cause unwanted odors in the air conditioned space as the foreign material is burned off Electrical wiring controls The electrical operation of each unit is determined by the component...

Page 30: ...to allow proper flow of condensate Failure to strictly follow this instruction will void the manufacturer s warranty and the manufacturer will not be responsible for any consequential damages due to w...

Page 31: ...activated drain pan clogged Remove debris from drain pan unclog pan unclog drain and emtpy Unit blows fuse when power is applied to unit Defective or improperly wired component Using a battery powered...

Page 32: ...operates but air delivery is low Incorrect fan speed has been selected Re select proper fan speed as required Dirty air filter Replace air filter Dirty coil Clean coil Obstruction in ductwork Check f...

Page 33: ...limit trips again check for the following conditions improper voltage to heating element obstructed fan or unit outlet reducing air flow over heating element dirty or defective heating element causing...

Page 34: ...grilles as required n n Flexible duct connections at unit n n Proper supply and return grille type and size n n Control outside air for freeze protection n n Insulate all ductwork as required Electric...

Page 35: ...of written consent from Zehnder Rittling the purchaser shall return the defective good s to the factory for inspection with freight prepaid If inspection shows the goods to be defective Zehnder Rittl...

Page 36: ...tling 100 Rittling Boulevard Buffalo NY USA 14220 T 844 934 6337 844 ZEHNDER F 716 827 6523 sales zehnder rittling com www zehnder rittling com Zehnder Rittling May 2015 English subject to change with...

Reviews: