background image

 

EN

 

11

 

Automatic operating mode 

 

Automatic operating mode requires an internal installation and configuration of a sensor module! The 
sensor modules inserted in the extract air section of the ventilation unit are available as optional 
accessories. 
The Automatic function changes into the frost protection operating mode in the event of frost protection 
criteria being met!   

The application of the Automatic function follows the logic of a demand controlled system for optimizing the indoor air 
quality. Consequently, an optimized response is achieved and mildew formation is prevented, which ultimately also leads 
to an increase in energy savings.  
The ComfoSpot 50 ventilation unit with a sensor module is classified in energy efficiency class A.  

2.3.1.1 

Functional principle of HUMIDITY sensor 

 

The HUMIDITY sensor module is primarily supposed to be installed in units for the ventilation of rooms 
with an increased occurrence of humidity.  

The HUMIDITY sensor module is equipped with a humidity and temperature sensor and calculates the relative humidity. 
In the evaluation of the current sensor signal for the setpoint selection, the fans are regulated in accordance with the 
characteristic curve in diagram 1. Since the dehumidification performance decreases the smaller the temperature 
difference between indoor and outdoor air, at a difference of 

Δ

T < 5 K the air volume is reduced to 20 m³/h. When the 

Bathroom function operating mode is active, the unit will be operated with the highest fan speed if the relative humidity 
amounts to 80% or more.  

 

LED4 flashes in 

alternation with the 

current fan speed 

Supply air mode 

Pressing the (+) button for 5 seconds in operating modes FS1 to FS4 
activates or deactivates the Supply air mode. The extract air fan is 
switched off; the supply air fan continues to run with the current fan speed. 

If the outdoor temperature falls below 13 °C, the extract air fan will be 
activated. 

The display for the current fan speed alternates every 2 seconds with the 
flashing LED4. 

 

Flashing of most 

recently active fan 

speed when supply 

air fan is switched 

off 

(Display of LED1-3 

as example) 

Frost protection 
mode 

 

A temperature threshold, which activates its own frost protection routine if 
not reached, is stored for each fan speed. The fan speed of the supply air 
will be regulated linearly between the minimum and maximum set point 
when the outside temperature is dropping. The fan speed can still be 
changed.   

The supply air fan is deactivated if a second temperature threshold is not 
reached.   

If the outside temperature falls below the temperature limit threshold of -15 °C, 
the extract air fan will also be deactivated and the unit switched off. 

After the unit is switched off, a flashing in those LEDs (by touching the (-) 
or (+) button) which denoted the most recently active fan speed will be 
signalled. The fan speed cannot be changed and is signalled with the 
flashing of Fault LED. 

 

Fault LED flashes 

Indication of 
locked modes 

If an inaccessible operating mode is selected, it will be signalled by the 
flashing of Fault LED.  

These operating modes are the locked standby, locked supply and extract 
air mode and complete switch-off due to frost protection. 

 

 LED Filter 

replacement flashes 

Indication of filter 
inspection 

The filters are monitored based on running time. 90 days are preset by 
default.  

After the filter runtime has elapsed, notification in regard of a filter 
inspection is signalled by the filter replacement LED flashing.  

Simultaneously pressing the (-) and (+) button for 3 seconds allows you to 
acknowledge the indication of the filter inspection and to reset the filter 
runtime.  

 

Fault LED lights up 

Error code LED1-4 

Signalling of error 
code fault 
message 

If an error occurs, this is signalled by the fault LED.  

Faults that can be diagnosed by the unit are symbolized by LED1-4 using 
an error code (see 3.4.1).  

Simultaneously pressing the (-) and (+) button for 3 seconds allows you to 
delete the indication of the fault notification. 

Summary of Contents for ComfoSpot 50

Page 1: ...Decorative Radiators Comfortable indoor ventilation Heating and cooling ceiling systems Clean air solutions Operating and installation instructions for user and installer Zehnder ComfoSpot 50...

Page 2: ...these documents is the property of Zehnder Group Publication as a whole or in parts requires the written approval of Zehnder Group In house duplication designated for the evaluation of the product or...

Page 3: ...tic operating mode 11 2 3 1 1 Functional principle of HUMIDITY sensor 11 2 3 1 2 Functional principle of CO2 VOC sensor 12 Maintenance by the user 12 Replacing the unit filters 13 Resetting the filter...

Page 4: ...and cleaning of enthalpy exchanger 28 Replacing the fans 30 Exchanging the control board 30 Visualization of fault notifications 31 Fault codes in the Fault status 31 Technical description 32 Dimensi...

Page 5: ...d compliance with this document including all safety instructions Unless otherwise stated in this manual only a recognized qualified person is authorized to install connect up commission and to servic...

Page 6: ...xplosion hazards When installing the unit make sure that the applicable country specific standards regulations for compliance with protection zones when installing electrical systems in rooms with a b...

Page 7: ...qual amount of fresh air is introduced into the same room via the outdoor supply air section on the inner casing of the unit An enthalpy exchanger which can transfer both humidity and heat owing to th...

Page 8: ...h in the four manual fan speeds and in the Automatic fan speed Item Description A Outside wall panel B EPP housing section pipe extension C EPP housing section with integrated power supply unit contro...

Page 9: ...nt buttons The external control panel has touch sensitive buttons and responds to touching the buttons The ComfoSpot 50 can be operated at the same time with the internal and the external control pane...

Page 10: ...tivated with a configured fan speed 1 The active operating time of the fan speed 1 of 15 30 or 45 min h can be set with a programming module by customer service Factory setting 60 min h FS1 permanent...

Page 11: ...the extract air fan will be activated The display for the current fan speed alternates every 2 seconds with the flashing LED4 Flashing of most recently active fan speed when supply air fan is switche...

Page 12: ...needed in accordance with the humidity or air quality control If both sensor modules are configured as active the control characteristic of the sensor module is designed with the greater sensor signa...

Page 13: ...o the Standby operating mode 2 Take off the interior top cover by disengaging the double locking connection available on both sides between the bottom and top cover of the interior top cover either on...

Page 14: ...bottom cover of the interior cover next to the filter compartment in each respective case Make sure that the filter is not pushed into the filter compartment with force 7 Insert the filter caps again...

Page 15: ...ualified personnel Installation requirements The following requirements must be assured for the correct installation Installation in accordance with the general and locally applicable safety and insta...

Page 16: ...nclosed instructions on professional installation when installing the wall mounting pipe A 230 VAC mains connection for fixed units is to be prepared on site for the mains power supply In order to con...

Page 17: ...to the wall mounting pipe whilst considering the position of the openings for the electrical connections If necessary a suitable tool can be used to remove the centring spring raised 5 mm and arranged...

Page 18: ...emented in accordance with the existing standards specific to the relevant country and must only be performed by qualified personnel 3 2 4 1 Connection for power supply Prior to starting work ensure t...

Page 19: ...el can be positioned for optimum accessibility either at the top or bottom of the interior cover of the unit depending on the ventilation unit s wall mounting height Relocating this can be done as fol...

Page 20: ...ing and into the bottom cover of the interior cover Pull the plug of the ribbon cable cautiously out of the post connection 4 Undo and remove the two screws for fastening the control panel carrier bri...

Page 21: ...he control panel when being placed onto the bottom cover of the interior cover 3 2 4 3 Connecting the external control panel The unit side connection of an optionally available external control panel...

Page 22: ...moved Colour coding connecting cable Clamping point for plug connection Colour coding Cable for external control panel white yellow A green B brown 3 Guide the connecting cable with the wire ends thro...

Page 23: ...nel as depicted Watch out for the correct assignment of the wires in accordance with the assignment of the plug connection 3 2 4 4 Installing and connecting the sensor module The installation and conn...

Page 24: ...the four nuts used to fasten the bottom cover of the interior cover to the EPP housing from the threaded bolts and remove the bottom cover including the electronic equipment cover 4 Remove the enthalp...

Page 25: ...lour coding for sensor cable SENSOR X8 clamping point Signal brown 1 white 2 green 3 CL yellow 4 DA 9 The four pin DIP switch MODE SW1 is used for the configuration of the Automatic function for the r...

Page 26: ...g time of fan speed 1 of 15 30 or 45 min h can be parameterized with a programming module Installing the outside wall panel For the installation of the outside wall panel one needs to make sure that a...

Page 27: ...he outside wall panel is still fitted tightly to the fa ade but this does not cause any deformation To protect against penetrating water the gap between the bottom cover of the outside wall panel and...

Page 28: ...without low quality filters the enthalpy exchanger must be cleaned immediately to restore the proper operation of the unit again Regardless of the maintenance for the unit the outside wall panel must...

Page 29: ...hold the EPP housing tight gripping the lower filter compartment 8 Clean the enthalpy exchanger if needed In doing so proceed as follows Dip the enthalpy exchanger several times in warm water max 40 C...

Page 30: ...rd whilst feeding in simultaneously In doing so do not damage the sealing tapes in the vicinity of the fans When exchanging the fans make sure that all the wires in the fan cables are disconnected pri...

Page 31: ...d install all parts whilst considering the restoration of all electrical connections in the reverse order 6 Restore the power supply Visualization of fault notifications The unit control system is equ...

Page 32: ...mounting pipe air passage openings laterally vertical on the interior cover and outside wall panel thumb wheel for shutter adjustment AT THE RIGHT Operation data Fan speed Volume flow Thermal efficie...

Page 33: ...mb wheel 50 50 335 300 380 370 330 Bottom cover for outer panel View from outside EHA ODA 330 360 Angular structural shell set View from outside Angular structural shell set View from inside 40 areas...

Page 34: ...EN 34 Terminal scheme...

Page 35: ...ork Enter date in quarter Change both filters in the HR unit recommended filter replacement cycle 90 days Quarter Year I II III IV 20 20 20 20 20 20 20 20 20 20 Quarter Year I II III IV 20 20 20 20 20...

Page 36: ...onal yes no 2 Electrical engineering control Cable connections and clamping assemblies secure yes no Are the regulating and control units functional yes no 3 Ventilation tube heat insulation Has clean...

Page 37: ...planned Cleaning option provided yes no yes no yes no 5 Extract air duct Cleaning option provided yes no 6 Extract air fan Cleaning option provided yes no 7 Control regulation system Operational yes...

Page 38: ...d very dirty Supply air Fan speed No Room name Project data Measurement data m h m s m h m s Extract air Fan speed No Room name Project data Measurement data m h m s m h m s Pel W The listed measureme...

Page 39: ...EN 39 Product data sheet...

Page 40: ...plicable for the ventilation system is based on the installation of the system and the model identifier from the product data sheet The product label shows the following details from the product data...

Page 41: ...omagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments EN 61000 6 3 2007 A1 2011 AC2012 A1 2011 Electromagnetic compatibility EMC...

Page 42: ...ehnder Group Deutschland GmbH Almweg 34 77933 Lahr Deutschland T 49 7821 586 392 F 49 7821 586 406 sales international zehndergroup com www international zehnder systems com PDE Manual_CS50_V1 8_V1117...

Reviews: