4 - EN
For safety reasons, the ComfoCool will pause for 15
minutes before initially activating the compressor.
ComfoAir 350 Luxe
ComfoAir 550 Luxe
5 Maintenance
5.1. Periodic maintenance
The heat exchangers, condensation tray and condensation
drain should be cleaned once every 4 years. Proceed as
follows:
1. Remove the plastic
front (A)
2. Remove the sheet steel
front (B)
3. Allow some room for the power cable and communi-
cations cable, and remove the
screen (C)
under the
evaporator
4. Pull the cooling
skid (D)
no more than 25 cm forwards.
5. Clean the evaporator, condenser and the condenser
tray with a mild cleaning agent. Take care not to dam-
age the evaporator and condenser fins. If the fins are
bent, they can be repaired with a fin-comb. Rinse the
cleaned components with water.