2.3.8 P menus for the user
Menu P1
¨
Status of programmes
Status
Sub-
menu
description
Activated
P11
Is menu 21 currently active?
Yes (1) / No (0)
P12
Is menu 22 currently active?
Yes (1) / No (0)
P13
Is menu 23 currently active?
Yes (1) / No (0)
P14
Is menu 24 currently active?
Yes (1) / No (0)
P15
Is menu 25 currently active?
Yes (1) / No (0)
P16
Is menu 26 currently active?
Yes (1) / No (0)
Menu P2
¨
Setting time delays
Time delay values
Sub-menu
description
Minimum
Maxi-
mum
General
reset
P21
(Optional)
Note:
only applies to systems
fitted with a corded switch
and a second switch in the
bathroom.
Delay timer for the bathroom switch (to switch to
high position).
• 'x' minutes after operating the bathroom switch,
the ComfoAir switches to the
high
setting
.
- Low voltage input
0 Min.
15 Min.
0 Min.
P22
(Optional)
Note:
only applies to systems
fitted with a corded switch
and a second switch in the
bathroom.
Overrun timer for the bathroom switch (to switch to
normal position).
• 'x' minutes after operating the bathroom switch,
the ComfoAir switches back to the
normal
setting
.
- Low voltage input
0 Min.
120 Min. 30 Min.
P23
(Optional)
Note:
only applies to systems
fitted with a hardwired
3-position switch.
Overrun timer for ventilation position 3 (using a
wired 3-position switch).
• If ventilation setting 3 (high) is switched on briefly
(< 3 sec), the ComfoAir will switch to the
high
set
-
ting
for 'x' minutes and then automatically returns
to the
normal
setting
.
If any 3-position switch is operated during this lag-
ging time the ComfoAir will instantly revert to the
ventilation position as set at that time.
0 Min.
120 Min.
0 Min.
P24
Filter warning
• 'x' weeks after cleaning the filters the "
filter
dirty
"
alert will reappear.
10 weeks 26 weeks
16
weeks
P25
Note:
only applies to systems fit-
ted with an rF switch.
Overrun timer for ventilation setting 3 (using "
").
• After pressing "
" briefly (< 2 sec.), the Com-
foAir will switch to the
high
setting for ‘x’ minutes
and then automatically returns to the
normal
set-
ting.
If any 3-position switch is operated during this lag-
ging time the ComfoAir will instantly revert to the
ventilation position as set at that time.
1 Min.
20 Min.
10 Min.