Zehnder EASY 5.0
46
Unit
Rea-
ding
Entry
Scaling
factor
Modbus
Factory
setting
Modbus
Type
Register
Modbus
Address
Modbus
Variable
Modbus
Address
BACnet
Details
Setpoint 1 CO
2
ppm
X
X
1
800
Holding
Register
1036
short
MSV,
31036
Only for DIVA and QUATTRO
versions
Setpoint 2 CO
2
ppm
X
X
1
900
Holding
Register
1038
short
AV,31038 Only for DIVA and QUATTRO
versions
Setpoint 3 CO
2
ppm
X
X
1
1000
Holding
Register
1040
short
AV, 31040 Only for DIVA and QUATTRO
versions
Fan balancing 1
CO
2
%
X
X
1
0%
Holding
Register
1037
short
AV, 31037 Only for DIVA versions
Fan balancing 2
CO
2
%
X
X
1
15%
Holding
Register
1039
short
AV, 31039 Only for DIVA versions
Fan balancing 3
CO
2
%
X
X
1
30%
Holding
Register
1041
short
AV, 31041 Only for DIVA versions
Fan balancing 1
CO
2
m
3
/h
X
X
0.1
See
details
Holding
Register
1037
short
AV, 31037
Only for QUATTRO versions,
factory setting depends on
machine model
Fan balancing 2
CO
2
m
3
/h
X
X
0.1
See
details
Holding
Register
1039
short
AV, 31039
Only for QUATTRO versions,
factory setting depends on
machine model
Fan balancing 3
CO
2
m
3
/h
X
X
0.1
See
details
Holding
Register
1041
short
AV, 31041
Only for QUATTRO versions,
factory setting depends on
machine model
Reading Entry
Type
Register
Modbus
Address
Modbus
Variable
Modbus
Address
BACnet
Details
Alarm presence
A/B/C
X
Input
Status
7
bool
BV, 20007 0=no alarm / 1=at least one alarm present
Class A alarm
presence
X
Input
Status
8
bool
BV, 20008 0=no alarm / 1=alarm present
Class B alarm
presence
X
Input
Status
9
bool
BV, 20009 0=no alarm / 1=alarm present
Class C alarm
presence
X
Input
Status
10
bool
BV, 20010 0=no alarm / 1=alarm present
Supply air fan fault
X
Input
Status
11
bool
BV, 20011 0=no alarm / 1=alarm present
Return air fan fault
X
Input
Status
16
bool
BV, 20016 0=no alarm / 1=alarm present
Supply/return
filter fault
X
Input
Status
63
bool
BV, 20063 0=no alarm / 1=alarm present
Internal battery
fault
X
Input
Status
88
bool
BV, 20088 0=no alarm / 1=alarm present
Electric coil
overheating fault
X
Input
Status
73
bool
BV, 20073
0=no alarm / 1=alarm present
Only for machine equipped with an
electric heating coil
16.6.3. Faults and alarms