Zehnder EASY 5.0
39
16.3. Modbus TCP communication
Activating communication via the Modbus TCP protocol requires the following parameters to be set manually if the
DHCP is not enabled:
If the DHCP is activated (factory setting), these parameters are assigned directly by the network when the TCP-IP port is
connected (see II PHYSICAL PRESENTATION OF THE CLD-283 CONTROLLER).
Access path to the function (Access level: Expert)
Step 1
→
Step 2
→
Step 3
→
Step 4
From
screen
Area to
click
Parameter
Possible value range
Baud rate
9600/14400/19200/28800/38400/57600/76800/115200
Address (slave)
1…247
Number of data bits
8
Parity
None/Even/Odds
Number of stop bits
1/ 2
IP Address
192,033,050,112
Gateway
192,033,050,005
DNS
192,033,050,040
Subnet mask
255,255,255,000
Modbus TCP - Bacnet IP
Main menu
Communication settings
Modbus RTU - Bacnet MS/TP
Modbus TCP - Bacnet IP
Protocol:
TCP/IP 1/2 port settings
Modbus TCP
Protocol:
Current IP:
Current Gateway:
Current DNS:
Current Subnet mask:
Modbus TCP
Z-MASTER-V1122-CSY-INM-Zehnder Easy5.0