3
For the installer - 29 - EN
3.10.2 Trouble shooting
Below are a number of trouble-shooting tips for the malfunction alerts described previously which can appear on
the digital operating devicein the event of a malfunction.
FilterI on
CC Ease panel
Disconnect
the power
Clean or
replace filters
Remount filters in the
ComfoAir with the rounded
part of the handle
facing downwards
Reconnect
the power
Press
until malfunction disappears
E1 / E2
Exhaust/supply fan
malfunction
Remove filters,
front and
metal cover
Does the fan connection
on the PCB
register 230 VAC?
Yes
Activate self-test
(P76 op 1)
Is fan control
voltage detectable
on PCB
(1.5 - 10 VDC)?
Yes
Disconnect the power
and remove exchanger
and foam part of bypass
and replace fan
No
Disconnect the power
and replace PCB
ATTENTION:
Reset unit!
No
ATTENTION!
Risk of electrocution:
do not touch the PCB,
the pre-heater
or the afterheater.
Disconnect the power
and replace PCB
ATTENTION:
Reset unit!