EN - 12 - For the user
Time delay values
Sub-menu
Description
Mini-
mum
Maxi-
mum
Default
P25
Note:
Only applies to systems
fi tted with an RF switch.
Overrun timer for ventilation setting
3 (using "
").
•
After pressing "
" BRIEFLY (<
2 sec.), the ComfoAir will switch
to the HIGH SETTING and auto-
matically switch back to the set
level after ‘x’ minutes.
1 Min.
20 Min.
10 Min.
P26
Note:
Only applies to systems
fi tted with an RF switch.
Overrun timer for ventilation setting
3 (using "
").
•
After pressing AND HOLDING "
" (> 2 sec.), the ComfoAir will
switch to the HIGH SETTING and
automatically switch back to the
set level after ‘x’ minutes.
1 Min.
120 Min.
30 Min.
P27
Note:
Only applies to systems
fi tted with a CC Ease panel.
Time for the Boost setting.
•
After pressing “
” continu-
ously (>2 sec.), the ComfoAir runs
at the high setting for ‘x’ minutes
and then automatically returns to
the programmed setting.
0 Min.
120 Min.
30 Min.
P29 (Optional)
N/a
1%
99%
10%
Menu P9 Status of programmes (from menu P5)
Ventilation programmes
Sub-menu
Description
Activated
P90
Open fi re programme active?
Yes (1) / No (0)
P91
Bypass Open (=Yes) / Closed (=No)?
Yes (1) / No (0)
P92
Geothermal heat exchanger valve
Open (=Yes) / closed (=No)
Yes (1) / No (0)
P93
Afterheater active?
Yes (1) / No (0)
P94
0 – 10 V programme active?
Yes (1) / No (0)
P95
Frost protection active?
Yes (1) / No (0)
P96
N/a
Yes (1) / No (0)
P97
Enthalpy programme active?
Yes (1) / No (0)