7.3 PUMP RELATED FAULT CODES
Co
de
ALARM
STRING
Mas-
ter
Sla-
ve
CONTROLLER
STATUS
DESCRIPTION
Condition that has to occur
to come out from alarm
status
Init
Stby Motor
running
28
"PUMP VMN
LOW"
X
X
X
X
Alarm: wrong voltage
output of pump chopper;
the motor voltage feedback
is not coherent with
applied PWM
-If the alarm is present in Init
status,remove the alarm
cause
-If the alarm has occurred in
stby or running mode, it is
necessary to remove the fault
cause and to activate a
function request
56 "PUMP STBY I
HIGH"
X
X
X
Alarm: in stby condition
(no PWM applied to pump
chopper), the pump
current sensor feedback is
out of the zero current
window
-If the alarm is present in Init
status,remove the alarm
cause
-If the alarm has occurred in
stby or running mode, it is
necessary to remove the fault
cause and to activate a
function request
242
Sla-
ve
"PUMP
TEMPERAT."
X
X
X
X
Warning: the pump
chopper temperature is
higher than 75°C
To remove warning cause
242
Ma-
ster
"PUMP"
X
X
X
X
Warning: Master controller
signals that Slave µC has
detected a fault in the
pump chopper
To remove warning cause
243
"PUMP INC.
START"
X
X
X
Warning: pump incorrect
start sequence
To remove warning cause
244 "PUMP VACC
MOTOR"
X
X
X
Warning: pump accelerator
voltage is 1V greater than
the minimum value
programmed
To remove warning cause
Summary of Contents for DUALAC2
Page 32: ...Page 32 4 9 MECHANICAL DRAWING Dimensions of Dualac2...
Page 33: ...Page 33 Dimensions of Dualac2 Power...
Page 34: ...Page 34 Dimensions of Dualac2 hp...
Page 35: ...Page 35 Dimensions of Dualac2 hp Power...
Page 36: ...Page 36 4 10 CONNECTION DRAWING DUALAC2 AND DUALAC2 POWER STANDALONE...
Page 37: ...Page 37 4 11 CONNECTION DRAWING DUALAC2 HP AND DUALAC2 HP POWER STANDALONE...
Page 40: ...Page 40 5 3 1 b Slave...
Page 41: ...Page 41 5 3 2 Dualac2 hp and Dualac2 hp Power menu configuration 5 3 2 a Master...
Page 42: ...Page 42 5 3 2 b Slave...