Page 80
24. THERMIC SENSOR KO
The range of inverter temperature sensor is always checked and a warning is signalled
if it is out of range.
When this alarm is signalled, the maximum current of the controller is reduced to halt.
25. WAITING FOR NODE #4
The Slave has detected a failure, the Master cannot close the main contactor because
of the alarm status of the Slave (which the Master knows by the CAN-BUS line). The
failure must be looked for in the Slave controller, use the remote console to get connec-
tion to the Slave µC.
26. WAITING FOR NODE #3
The Master µC has detected a fault condition, the Slave is aware of this thanks to
canbus communication; it cannot drive the motor until the Master has resolved its
problem. The fault has to be looked for in the Master.
27. NO CAN MESSAGE #4
Master (node #3) signals that it has lost can communication with the Slave (node #4).
This fault could be determined by a problem in the truck canbus line or by an internal
problem in the controller logic card.
It is suggested to preliminary check canbus connection.
28. NO CAN MESSAGE #3
Slave (node #4) signals that it has lost can communication with the Master (node #3).
This fault could be determined by a problem in the truck canbus line or by an internal
problem in the controller logic card.
It is suggested to preliminary check canbus connection.
Summary of Contents for DUALAC2
Page 32: ...Page 32 4 9 MECHANICAL DRAWING Dimensions of Dualac2...
Page 33: ...Page 33 Dimensions of Dualac2 Power...
Page 34: ...Page 34 Dimensions of Dualac2 hp...
Page 35: ...Page 35 Dimensions of Dualac2 hp Power...
Page 36: ...Page 36 4 10 CONNECTION DRAWING DUALAC2 AND DUALAC2 POWER STANDALONE...
Page 37: ...Page 37 4 11 CONNECTION DRAWING DUALAC2 HP AND DUALAC2 HP POWER STANDALONE...
Page 40: ...Page 40 5 3 1 b Slave...
Page 41: ...Page 41 5 3 2 Dualac2 hp and Dualac2 hp Power menu configuration 5 3 2 a Master...
Page 42: ...Page 42 5 3 2 b Slave...