36
Error Code
(7- Segment)
Outdoor unit led
Compressor excessive current protection
(if it occurs during first start)
ER 14
Blinking 8/13 times - stopping for 3 sec.
Error Code
(7 Segment)
Outdoor unit led
Outdoor environment sensor is open or
short-circuit
ER 15
Blinking 16 times - stopping for 3 sec.
Error Code
(7- Segment)
Outdoor unit led
Compressor discharge sensor is open or
short-circuit
ER 16
Blinking 17 times - stopping for 3 sec.
Error Code
(7 Segment)
Outdoor unit led
Outdoor unit setting not performed/
deleted
ER 18
Error Code
(7 Segment)
Outdoor unit led
Low/high voltage protection
ER HL
Blinking 18 times - stopping for 3 sec.
The product gives ER 14 error when
it is first given energy (Compressor
current protection)
Outdoor unit LED signals first 8 times,
then 13 times
Do the controls specified for ER 11.
Outdoor unit gives ER 15 error after
operating (Outdoor unit environment
Replace the outdoor unit sensor group.
Outdoor unit gives ER 16
error after
operating (compressor discharge
temperature sensor error)
Replace the outdoor unit sensor group.
Air conditioner gives ER 18 error.
Outdoor unit board’s type code is
deleted.
Replace the outdoor unit control board.
Air conditioner gives ER HL error. It is
an error for low/high voltage.
Outdoor unit LED signals 18 times.
Check the network voltage values.
Does the voltage continuously fluctuate
or is it above/below the limits?
Product is normal. Product will start to
operate after voltage values return to
normal.
YES
NO
Check the reactor cables. Is there
a disconnection or looseness in the
cables?
Check the cables.
YES
NO
Replace the outdoor unit control board.