35
Error Code
(7 Segment)
Outdoor unit led
Compressor excessive current protection
(if t occurs during operation)
ER 13
Blinking 13 times - stopping for 3 sec.
Outdoor unit gives ER 13 error after
operating (Compressor current
protection)
Outdoor unit LED signals 13 times
Check the indoor unit dust filters. Are
they clean?
Clean the dust filters and place them.
NO
YES
Are the indoor and outdoor unit suction
and blowing
Resolve the situations blocking heat
flow and re-operate
YES
NO
Does the outdoor unit fan motor work?
Check the fan motor. Replace if it is
faulty
NO
YES
Check the exchangers. Are they so
dirty that they block air flow?
Check the fan motor. Replace if it is
faulty.
YES
NO
Check the cables going from the board
to the compressor. Is there a cross
connection? Is there a looseness,
displacement in cables?
Correct the cables going to the
compressor.
YES
NO
Replace the outdoor unit control board.