background image

Install-TOMMI - JUN_2020 - 2020-06-18.docx                  www.yunca.co.nz  

Page 13 of 15 

13. 

Take the painted Drop Box and conduct a trial fitting of it up into the Ceiling Tile Frame. Confirm that: 
 

13.1. 

It can be made vertical. (Perpendicular to the floor.) 

 

13.2. 

It can be positioned at the correct height vertically to cope with: Floor Pro height of 
 height of Tommi + length of available Flue Guard and still have the Flue Guard lap 
neatly onto the lower portion of the Drop Box. 

 

13.3. 

The Drop Box is centralised over the floor mark position for the fire. 

 

14. 

Mark the midpoint of each side of the Drop Box and use masking tape across to find the centre. 

 

15. 

Check position with plumb bob or laser etc. You have some latitude to enlarge the hole and move the 
Ceiling Tile Frame up or down the ceiling slope as required. You may temporarily install the two halves 
of the Ceiling Tile 

– as described below – to determine where the Drop Box has to sit. 

 

16. 

Put  a  couple  of  temporary  screws  through  the  centre  holes  of  the  Drop  Box  and  Ceiling  Tile  frame 
flanges, allowing for perpendicular adjustment front to back (

Caution:

 These centre screws must be 

removed once rivets are fixed in the outer holes, as they would otherwise inhibit the flue from sitting in 
the proper position). 
 

17. 

Mark position of Drop Box relative to Ceiling Tile Frame 

– vertically and up and down slope. 

 

18. 

When everything is positioned correctly, remove Drop Box and permanently install Ceiling Tile Frame 
with 3 screws through round holes in each tab, each side into blocking timber. 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 5 

 
 
 
 
 
 

Summary of Contents for TOMMI

Page 1: ...d in the Operations Manual Using it in any manner not recommended by the manufacturer may result in injury or death FOR UNITS INCLUDING ELECTRICAL CONNECTIONS If the wood burner is permanently connected to an electrical source an isolating switch wall switch must be installed New circuits or modifications may be made if required but must be made using the services of a certified electrician only E...

Page 2: ...ing by the testing authority is considered to be in breach of the approval granted for compliance with AS NZS 4013 V Mixing of appliance or flue system components from different sources or modifying the dimensional specification of components may result in hazardous conditions Where such action is considered the manufacturer should be consulted in the first instance VI Cracked and broken component...

Page 3: ...0mm at 475mm or higher above the floor 2 Extend at least 200mm from each side of the fuel loading or ash removal opening unless it forms an abutment with a wall or heat shield at a lesser distance 3 Be constructed of 2 sheets of non combustible materials such as one of the following examples or similar The total combined thickness must not be less than 20mm Examples Hilux 2 x 12mm Eterpan 2 x 15mm...

Page 4: ...se Note All flue joints must be sealed with flue sealing compound Use stainless steel screws or rivets to join the active flue pipe three equally spaced places at each joint The first length of active flue must be fixed to the flue spigot on the burner with at least one stainless steel screw or rivet The required minimum flue termination height is 4 6m above the floor protector G TOMMI WOODBURNER ...

Page 5: ...Install TOMMI JUN_2020 2020 06 18 docx www yunca co nz Page 5 of 15 FIG A HEATER DIMENSIONS TOMMI WOODBURNER Not to Scale ...

Page 6: ...Install TOMMI JUN_2020 2020 06 18 docx www yunca co nz Page 6 of 15 FIG B HEATER POSITION TOMMI WOODBURNER Not to Scale ...

Page 7: ...Install TOMMI JUN_2020 2020 06 18 docx www yunca co nz Page 7 of 15 FIG C TOMMI FREESTANDING WOODBURNER TYPICAL FLUE INSTALLATION ...

Page 8: ...ACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AS NZS 4013 D MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS WHERE SUCH ACTION IS CONSIDERED THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE E CRACKED AND BROKEN COMPONENTS E G GLASS PANELS OR FIRE BRICKS MAY RENDER THE INSTALL...

Page 9: ...Install TOMMI JUN_2020 2020 06 18 docx www yunca co nz Page 9 of 15 FIG E MAIN AIR INTAKE DUCT ASSY Not to scale ...

Page 10: ...d that this is where the fire should sit 3 Transfer this floor position mark to the ceiling directly above using a plumb bob laser or other means Mark a line from this point up and down the slope of the ceiling and a line through the point across the slope forming a cross 4 Accurately determine the actual slope of your ceiling Using the numbers from the supplied Ceiling Tile Frame Cut Out chart ma...

Page 11: ...imum clearance to the walls at each side is 400mm This is achieved with a parallel distance from each wall to the centre of the flue of 879mm See Fig 2 below Fig 2 Plan View Tommi Installed Diagonally Fig 3 Sloped Ceiling Frame Opening Dimensions ANGLE OPENING W x L 0 335 x 335 5 335 10 340 15 345 20 355 25 370 30 385 35 410 40 435 45 475 ...

Page 12: ...iling Tile Frame and is correctly positioned up and down slope 9 Cut out the ceiling rectangle You can cut around the outside of the line 10 Confirm the Ceiling Tile Frame will fit in the hole and looks appropriate 11 Frame out the sides of the cut out from within the room or from the ceiling cavity if you have access to support the sides of the Ceiling Tile Frame when installed 12 Install the Cei...

Page 13: ...lumb bob or laser etc You have some latitude to enlarge the hole and move the Ceiling Tile Frame up or down the ceiling slope as required You may temporarily install the two halves of the Ceiling Tile as described below to determine where the Drop Box has to sit 16 Put a couple of temporary screws through the centre holes of the Drop Box and Ceiling Tile frame flanges allowing for perpendicular ad...

Page 14: ... REAR Ceiling Tile in position against the Ceiling Tile Frame from the down slope side of the flue or the side closest to the wall and press push pin into the socket Note There is no sliding flange on rear inner ceiling tile it may droop slightly 21 1 Slide the Outer upper Ceiling Tile into the slots of the Ceiling Tile Frame on the upper side of the flue Move the two halves together such that the...

Page 15: ...touches the Drop Box You can do this from within the ceiling cavity above the ceiling if you have access otherwise do it from within the room below the ceiling 25 Before installing any more sections of Liner and while you can still see the spacers connect the first sections of Inner and Outer Liner together by drilling right through the Outer Liner and spacers and installing screws or rivets This ...

Reviews: