CONNECTION TO GAS SUPPLY AND TESTING PRESSURES
GAS SUPPLY:
Burn only the fuel for which the appliance is equipped. The data plate affixed to the base of the appliance
specifies the gas type, which the appliance is factory equipped for.
CONNECTION:
The gas inlet is a 3/8” BSP pipe.
A separate gas isolation valve should be installed immediately up stream of the
connection to the appliance.
Important:
Gas Pipe sizing:
The supply pipe size should be determined from NZS 5261 to
ensure correct gas supply to the appliance. Incorrect pipe sizing
WILL
affect the performance of this
appliance.
WARNING:
To stop pipe compounds entering the gas line, do not apply sealing compounds to the
first two threads at the tip of any gas connection. All joints should be tested for leaks before operating the
fire.
Gas pressure requirements:
Correct gas pressure and the use of a properly sized gas supply line are essential for the safe and efficient
performance of this appliance. The inlet and outlet pressures at the control must be tested on installation.
Note: Improper gas pressure will affect fire performance, flame colour or cause pilot malfunction.
Natural Gas:
Input
930:
53 MJ,
730:
50 MJ,
Minimum inlet pressure
1.25 kPa (5"w.g.)
Maximum inlet pressure
5.0 kPa (20"w.g.)
Max Manifold Operating pressure
0.6 kPa with Burners on HIGH
0.25 kPa with Burners on LOW
LPG:
Input
930 & 730:
48 MJ
Minimum inlet pressure
2.75 kPa (11"w.g.)
Maximum inlet pressure
3.5 kPa (14"w.g.)
Max Manifold Operating pressure
1.5 kPa with Burners on HIGH
0.7 kPa with Burners on LOW
CAUTION: Do not use this appliance if any part has been water damaged or exposed to
moisture causing corrosion.
A Qualified service technician should inspect the appliance and replace any part of the
gas system that has been water damaged.