INSTRUMENT INSTALLATION AND WIRING DIAGRAM 

Panel dimension A1, B1, E1 or F1 

 

 

 

 

 

      Panel dimension A, B, E or F 

                       

 

 

The diagram illustrated is for upright panel dimension A/A1/E/E1.   

 

 

 

For panel dimension B/B1/F/F1, please rotate the diagram clockwise by 90 degree

.   

 

 

 

Panel dimension D (72 x 72mm)

 

 

 

 

 

 

   

Panel dimension D1/D2 (48 x 48mm) 

                     

 

 

Remarks 

1. 

Thermocouples  compensate  wires  should  be  directly  screwed  to  the  back  of  the  instrument.  No  extension  by  normal 

conducting wire should be used. Please pay attention to the polarity of the compensate wires.

 

2. 

The solid-state relay (SSR) externally connected should provide 2300 V isolation between input/output-to-power line. 

(CE requirement) 

Main Output 

Alarm Output 

Main Output 

Alarm Output 

Summary of Contents for AI-218

Page 1: ...Automation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 218 Opera...

Page 2: ...Multiple thermocouples and RTDs are selectable Maximum support two alarms contact output Universal supply power 100 240VAC 50Hz 60Hz 2 Part 2 Front panel dimension Panel Size Front Panel width height...

Page 3: ...tput L5 Dual relay output module Output module Capacity 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to relay output L or S...

Page 4: ...s The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press will access System Parameter Table See V PARAMETER AND SETT...

Page 5: ...o 808 and press to unlock the System Parameter Table 0 255 0 System Parameter Table Loc 808 to unlock AHYS Alarm Hysteresis Avoid frequent alarm on off action because of the fluctuation of PV AHY 2 by...

Page 6: ...ction in ON OFF control mode PV SV Output turns OFF Relay opens PV SV CHY Output turns ON Relay closes 0 200 InP Input specification Thermocouples RTD 0 K 1 S 2 R 4 E 5 J 7 N 21 Pt100 0 21 0 dPt Resol...

Page 7: ...nel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermocouples compensate wires should be directly screwed...