42
YT-3400/3450 series
7.8.7
Custom Zero Setting Mode (CST ZERO)
Custom Zero Setting Mode allows the user to set any specific point as zero position. For
example, the zero point can be set at input signal of 7mA.
7.8.8
Custom End Setting Mode (CST ENd)
Custom End Setting Mode allows the user to set any specific point as end position. For
example, the end point can be set at input signal of 11mA.
The difference between zero
and end point must be greater or equal to 4mA.
⇨
<ENTER>
⇨
<DOWN>
6 times
⇨
<ENTER>
⇨
<UP>/<DOWN>
<ENTER>
⇨
<ESC>
3 times
⇨
<ENTER>
⇨
<DOWN>
7 times
⇨
<ENTER>
⇨
<UP>/<DOWN>
<ENTER>
⇨
<ESC>
3 times