37
YT-3400/3450 series
7.7.2
Zero-Point (TR_ZERO) and End-Point
(TR_END) for Transmitter
TR_ZERO adjusts the zero point of the
transmitter
(4-20mA
feedback),
and
TR_END adjusts the end point of the
transmitter (4-20mA feedback)
7.7.3
Normal / Reverse Feedback Signal (TR NORM / REVS)
The feedback signal from the positioner can be changed to normal or reverse.
⇨
<DOWN>
⇨
<ENTER>
⇨
<UP>/<DOWN>
<ENTER>
Zero Adjustment
Match feedback
signal with 4mA
⇨
<ESC>
⇨
<DOWN>
⇨
<ENTER>
End Adjustment
⇨
<UP>/<DOWN>
<ENTER>
⇨
<ESC>
Match
feedback
signal with 20mA
⇨
<ENTER>
⇨
<DOWN>
5 times
⇨
<ENTER>
⇨
<DOWN>
⇨
<ENTER>
⇨
<ESC>
3 times