44
YT-3400/3450 series
7.9
Diagnostic (dIAGNO)
7.9.1
PST Introduction
When
PST
runs by
PST NOW
or
SCHD,
if valve position is in the range of
TOL
from
START
PO
, Positioner supply or vent air until the valve reach the
TARGET 1, 2.
But
PST
test will
stop if valve position goes out of the
TOL
or doesn’t reach
TARGET1, 2
within the
LIMIT TM
.
After the valve position reach the
TARGET 1, 2,
the valve will pause during the
LATENCY
and move back to the
START PO
. The valve will be under ready state during the
INTERVAL
time after completing 1 cycle of
PST
in the
SCHD
mode.
⇨
<ENTER>
6 seconds
⇨
<DOWN>
5 times
TOL
START PO
TARGET 1
TARGET 2
LATENCY
INTERVAL