Young ResponseONE 91000 Instructions Manual Download Page 7

 Page 4

91000-90(B)

5.1.1  ASCII

ASCII output format provides continuous measurement data in text 

format at any of the available baud rates.

The wind measurement in ASCII output appears either in POLAR 

(default) or CARTESIAN UV format.  With POLAR format, the wind 

speed  threshold  and  wind  speed  units  are  user-selectable.  With 

CARTESIAN  the wind threshold is ignored and wind speed units 

are always meters per second (m/s).

ASCII POLAR FORMAT

 

a www.ww ddd.d ss*cc<CR>

where:

a

  

= Sensor address

www.ww

  

= Wind speed

ddd.d

 

= Wind direction

ss

 

= Status code

*

 

= Asterisk (ASCII 42)

cc

 

= Checksum

<CR>

 

= Carriage return (ASCII 13)

ASCII CARTESIAN (UV) FORMAT

 

a uu.uu vv.vv ss*cc<CR>

where:

a

  

= Sensor address

±uu.uu

  

= U-axis wind speed (m/s)

±vv.vv

  

= V-axis wind speed (m/s)

ss

 

= Status code

*

 

= Asterisk (ASCII 42)

cc

 

= Checksum

<CR>

 

= Carriage return (ASCII 13)

CHECKSUM  is  a  two-character  hexadecimal  value  (in  printable 

ASCII format) generated by taking the exclusive-or of all characters 

up to the asterisk. STATUS CODE shows a non-zero value when the 

sensor cannot acquire sufficient samples or a measurement error has 

occurred.  See APPENDIX C for more information on status codes.

5.1.2  ASCII POLLED

ASCII  POLLED  is  like ASCII  format  described  above  except  just 

one serial output string is sent for each polling command received. 

The polling command is 

Ma!

 where 

'a'

 is the sensor address (valid 

characters: 0-9, A-Z, a-z). The default address is 

'0'

 (ASCII 48).

5.1.3  RMYT

RMYT is a 6-byte binary data format sent at 9600 baud using RS-485 

OUTPUT ONLY mode. It is for use with the YOUNG Model 06201 

Wind Tracker.

5.1.4  NMEA

NMEA  format  provides  continuous  measurements  in  standard 

NMEA marine sentences at 4800 baud. The 

ResponseONE

 must be 

connected to a NMEA-capable device. Specific details of the NMEA 

data string are below:

NMEA FORMAT

$WIMWV,ddd,R,www.w,u,A*cc<CR><LF>

where:

WI

 

= Device type (weather instrument)

MWV

 

= Wind direction and speed

ddd

 

= Wind direction (degrees)

www.w

 

= Wind speed

u

 

= Wind speed units

 

 

S = mph

 

 

N = knots

 

 

K = kmph

 

 

M = m/s

A

 

= Data status code: A=valid, V=invalid

*

 

= Asterisk (ASCII 42)

cc

 

= Checksum

<CR><LF>

 

= Carriage return,Line feed (ASCII 13,10)

CHECKSUM  is  the  two-character  printable  hexadecimal  value  

generated by taking the exclusive-or of all characters between 

'$'

 

and 

'*'

.

5.2  SDI-12

SDI-12 stands for serial data interface at 1200 baud.  It is often used 

to  interface  battery  powered  data  recorders  with  microprocessor 

based devices designed for environmental data acquisition.  SDI-

12 is typically used when low power usage is required. The SDI-12 

device normally remains in a low power, standby state until it is polled 

at which time a measurement is sent.  SDI-12 can effectively address 

multiple sensors on the same cable.

5.2.1  SDI-12 MEASUREMENT COMMANDS

Model  91000  uses  the  SDI-12  (v1.3)  serial  communication protocol  

to  initiate  measurements  and  set  sensor  operation parameters.  

The  default  sensor  address  is  0  (zero),  and  can  be changed  to  

any  valid  single-character  value  if  needed. Additional details about 

the SDI-12 protocol may be found at 

www.sdi-12.org

.

After  initial  power-up  with  12  VDC,  the  sensor  is  in  a  low-

power standby state with a quiescent current of 4.2 mA.  A valid and 

properly addressed SDI-12 command wakes the sensor to initiate a 

measurement, set or check operating parameters. After command 

processing has finished, the sensor returns to the low-power standby 

state. 

SDI-12  'M'  or  'C'  commands  initiate  a  measurement.  The  sensor 

response  message  indicates  the  maximum  time  needed  before 

the measurement is ready, and data values will be available. The 

maximum time ranges from 1 to 5 seconds depending on the Sample 

Count.

If  an  'M'  command  initiates  a  measurement,  the  sensor  sends  a 

Service Request when the measurement is ready to be retrieved. 

When the polling device receives the Service Request it then sends 

a  'D'  command  to  request  measurement  results  from  the  sensor. 

With  'C'  commands,  no  Service  Request  is  sent,  and  the  polling 

device must wait the full delay time before sending the 'D' command 

to request the measurement.

Summary of Contents for ResponseONE 91000

Page 1: ...91000 ULTRASONIC ANEMOMETER METEOROLOGICAL INSTRUMENTS INSTRUCTIONS R M YOUNG COMPANY 2801 AERO PARK DRIVE TRAVERSE CITY MICHIGAN 49686 USA TEL 231 946 3980 FAX 231 946 4772 WEB www youngusa com PN 91...

Page 2: ...pose Communications Program 6 6 3 Command Overview 7 6 4 Command Details 7 7 0 EXAMPLE SETTINGS 9 8 0 EMC COMPLIANCE 9 9 0 WARRANTY 9 10 0 CE COMPLIANCE 9 APPENDIX A WIRING CONNECTIONS A1 RS 232 Seria...

Page 3: ......

Page 4: ...seONE tm Ultrasonic Anemometer is a 2 axis no moving parts wind sensor It is ideal for general meteorological applications requiring accurate and reliable measurement The sensor features wide operatin...

Page 5: ...round a structure is disturbed to 10 times the height of the structure downwind and 1 1 2 times the height of the structure above the roof 10H 1 5 H H OPEN LEVEL GROUND Fig 4 1 Wind Siting Considerati...

Page 6: ...asurement A declination value can be entered using the ResponseONE CONFIG program or it can be compensated in the data logger program Please note that declination may change if the sensor is moved to...

Page 7: ...tion degrees www w Wind speed u Wind speed units S mph N knots K kmph M m s A Data status code A valid V invalid Asterisk ASCII 42 cc Checksum CR LF Carriage return Line feed ASCII 13 10 CHECKSUM is t...

Page 8: ...nn nnn Sample Count 001 800 samples aXS S nnn CR LF aXS ERR S 001 800 ONLY CR LF aXMnnnnn nnnnn WS multiplier x 10000 00000 30000 aXM M nnnnn CR LF aXM ERR M 00000 30000 ONLY CR LF aXTnnn nnn Wind Spe...

Page 9: ...1 in APPENDIX A Factory default sensor baud rate is 9600 Configure the serial communications program for NO handshaking and 1 start 8 data 1 stop bit no parity no flow control The sensor must be in CO...

Page 10: ...hen on again to operate properly SDI 12 automatically sets baud rate to 1200 and disables RS 232 and RS 485 SET03nn Set the baud rate for RS 232 RS 485 serial communication Default value is 96 Note Ba...

Page 11: ...ire a longer output interval SET13n Set ASCII output format Determines whether ASCIIandASCIIPOLLEDserialoutputsprovide wind data in either Polar speed and direction or Cartesian UV form Default is Pol...

Page 12: ...ested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when...

Page 13: ...cal DB 9 RS 232 Connection Z SDI Y TX B RX A REF PWR PWR EARTH GND WHT BLU GRN ORG BRN RED BLK Earth Ground Supply Voltage 10 30 VDC 80mA max Sensor TX Z Inverted signal Sensor TX Y Non inverted signa...

Page 14: ...lor code is for Young 18446 Cable Figure A3 RS 485 RS 422 SERIAL CONNECTION HALF DUPLEX Serial Device SETTINGS Output Mode RS 485 Output Only Output Format ASCII or NMEA Baud Rate 1200 4800 9600 19200...

Page 15: ...Full Duplex Output Format ASCII ASCII POLLED or NMEA Baud Rate 1200 4800 9600 19200 or 38400 Set 26800 Translator baud rate to match ResponseONE Use shielded cable Connect cable shield to earth groun...

Page 16: ...ble Figure A7 06201 WIND TRACKER SETTINGS Output Mode RS 485 Output Only Output Format NMEA Baud Rate 4800 Use shielded cable Connect cable shield to earth ground as shown Color code is for Young 1844...

Page 17: ...ION 80 mm ORIENTATION RING N W E S JUNCTION BOX 270 90 180 POLAR WIND SPEED WIND DIRECTION 0 EXAMPLE WIND AT 45 V m s WIND FROM NORTH CARTESIAN U V U m s WIND FROM EAST APPENDIX B SENSOR ORIENTATION A...

Page 18: ...then the poll command is 0M in SDI 12 mode and M0 in ASCII Polled mode Acquire the sensor with the ResponseONE CONFIG program see section 6 2 and verify setup mode Direction is incorrect If compass i...

Reviews: