518676-BIM-C-0610
Johnson Controls Unitary Products
43
ZS-10 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
675
0.53
726
0.74
776
0.94
824
1.12
870
1.30
914
1.48
957
1.65
1000
1.82
1041
1.99
1082
2.17
2800
686
0.63
738
0.84
787
1.04
835
1.23
881
1.41
925
1.58
969
1.76
1011
1.93
1052
2.10
1093
2.27
3000
699
0.75
750
0.96
800
1.16
847
1.34
893
1.52
938
1.70
981
1.87
1024
2.04
1065
2.21
1106
2.39
3200
713
0.88
764
1.09
814
1.28
861
1.47
907
1.65
952
1.83
995
2.00
1037
2.17
1079
2.34
1119
2.52
3400
728
1.02
779
1.23
829
1.43
877
1.61
923
1.79
967
1.97
1010
2.14
1053
2.31
1094
2.48
1135
2.66
3600
745
1.18
796
1.39
846
1.59
893
1.77
939
1.95
984
2.13
1027
2.30
1069
2.47
1111
2.64
1152
2.82
3800
763
1.36
815
1.57
864
1.76
912
1.95
958
2.13
1002
2.31
1046
2.48
1088
2.65
1129
2.82
1170
3.00
4000
783
1.55
835
1.76
884
1.96
932
2.15
978
2.33
1022
2.50
1066
2.67
1108
2.84
1149
3.02
1190
3.19
4200
805
1.77
856
1.98
906
2.17
953
2.36
999
2.54
1044
2.72
1087
2.89
1129
3.06
1171
3.23
1211
3.41
4400
828
2.00
879
2.21
929
2.41
976
2.59
1022
2.77
1067
2.95
1110
3.12
1152
3.29
-
-
-
-
4600
852
2.25
904
2.46
953
2.66
1001
2.85
1047
3.03
1092
3.20
1135
3.37
-
-
-
-
-
-
4800
879
2.52
930
2.73
980
2.93
1027
3.12
1073
3.30
-
-
-
-
-
-
-
-
-
-
5000
906
2.81
958
3.02
1007
3.22
1055
3.41
-
-
-
-
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
ZS-12 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
Standard 3 HP & Drive
3200
684
1.00
741
1.16
794
1.32
844
1.48
892
1.65
940
1.81
988
1.97
1036
2.12
1087
2.27
1141
2.42
3400
709
1.15
765
1.30
818
1.46
868
1.62
916
1.79
964
1.95
1012
2.11
1061
2.26
1112
2.42
1166
2.56
3600
734
1.30
791
1.46
844
1.62
894
1.78
942
1.94
990
2.10
1038
2.26
1087
2.42
1137
2.57
1191
2.72
3800
761
1.48
818
1.63
871
1.79
921
1.95
969
2.12
1017
2.28
1065
2.44
1114
2.59
1164
2.75
1218
2.89
4000
789
1.66
846
1.82
899
1.98
949
2.14
997
2.31
1045
2.47
1093
2.63
1142
2.78
1192
2.93
1246
3.08
4200
818
1.87
875
2.03
928
2.19
978
2.35
1026
2.51
1074
2.67
1121
2.83
1170
2.99
1221
3.14
1275
3.29
4400
847
2.09
904
2.25
957
2.41
1007
2.57
1055
2.73
1103
2.90
1151
3.06
1199
3.21
1250
3.36
1304
3.51
4600
877
2.33
934
2.49
986
2.65
1036
2.81
1085
2.97
1132
3.14
1180
3.29
1229
3.45
1280
3.60
1334
3.75
4800
907
2.59
963
2.75
1016
2.91
1066
3.07
1115
3.23
1162
3.39
1210
3.55
1259
3.71
1310
3.86
1364
4.01
5000
937
2.86
993
3.02
1046
3.18
1096
3.34
1145
3.50
1192
3.66
1240
3.82
1289
3.98
1340
4.13
1394
4.28
5200
967
3.15
1023
3.31
1076
3.47
1126
3.63
1175
3.79
1222
3.95
1270
4.11
1319
4.27
1370
4.42
1424
4.57
5400
997
3.45
1053
3.61
1106
3.77
1156
3.93
1205
4.09
1252
4.26
1300
4.41
1349
4.57
1400
4.72
1454
4.87
5600
1027
3.77
1083
3.93
1136
4.09
1186
4.25
1235
4.41
1282
4.57
1330
4.73
1379
4.89
1430
5.04
1484
5.19
5800
1057
4.11
1113
4.26
1166
4.42
1216
4.59
1264
4.75
1312
4.91
1360
5.07
1409
5.22
-
-
-
-
6000
1086
4.46
1143
4.61
1196
4.77
1246
4.93
1294
5.10
1342
5.26
-
-
-
-
-
-
-
-
6200
1116
4.82
1172
4.98
1225
5.14
1275
5.30
-
-
-
-
-
-
-
-
-
-
-
-
Hi Static 5 HP & Drive
5 HP & Field Supplied Drive