Unitary Products Group

Guide Specifications

General

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's ZJ/XP units are convertible single package units. 
Although the units are primarily designed for curb mounting on 
a roof, they can also be slab-mounted at ground level or set on 
steel beams above a finished roof. Cooling only, cooling with 
gas heat and cooling with electric heat models are available 
with a wide variety of factory-mounted options and field-
installed accessories to make them suitable for almost every 
application. All units are self-contained and assembled on full 
perimeter base rails with holes in the four corners for overhead 
rigging. Every unit is completely piped, wired, charged and 
tested at the factory to simplify the field installation and to 
provide years of dependable operation. All models (including 
those with an economizer) are suitable for either bottom or 
horizontal duct connections. Models with power exhaust are 
suitable for bottom duct connections only. For bottom duct, 
remove the sheet metal panels from the supply and return air 
openings through the base of the unit. For horizontal duct, 
remove the supply and return air panels on the rear of the unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit includes 
a 75 VA transformer, a 24-volt circuit breaker and a relay board 
with a compressor lockout circuit, a terminal strip for thermostat 
wiring, plus an additional set of pin connectors to simplify the 
interface of additional field controls. All models are CSA listed. 
All models include a 1-year limited warranty on the complete 
unit. Compressors and electric heater elements carry a 5-year 
warranty. Aluminized steel and Stainless steel tubular heat 
exchangers carry a 10-year warranty.

Description

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat, Heat 
Pump/Optional Electric Heat and are designed for outdoor 
mounted installation.

The 3 ton, 4 ton and 5 ton units shall have minimum SEER rat-
ing of 13.0 with heat pumps having a 7.7 H.S.P.F. They shall 
have built-in field convertible duct connections for down dis-
charge supply/return or horizontal discharge supply/return, and 
be available with factory installed options or field installed 
accessories. The units shall be factory wired, piped, charged 
with R-410A refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All units the 
cooling performance shall be rated in accordance with DOE 
and ARI test procedures. Units shall be CSA listed, classified to 
ANSI Z21.47, UL 1995/CSA No. 236 standards.

Unit Cabinet

Unit cabinet shall be constructed of G90 galvanized steel, with 
exterior surfaces coated with a non-chalking, powdered paint 
finish, certified at 1000 hours salt spray test per ASTMB117 
standards. Indoor blower section shall be insulated with a 
minimum 1/2” thick insulation, coated on the airside. Aluminum 
foil faced insulation shall be used in the furnace compartment 
and be fastened with ridged fasteners to prevent insulation from 
entering the air stream. Cabinet panels shall be “large” size, 
easily removable for servicing and maintenance. Full perimeter 
base rails shall be provided to assure reliable transit of 
equipment, overhead rigging and proper sealing on roof curb 
applications. Disposable 1" filters shall be furnished and be 
accessible through a removable access door, sealed airtight. 
Units filter track shall be designed to accommodate either 1" or 
2" filters. Fan performance measuring ports shall be provided 
on the outside of the cabinet to allow accurate air 
measurements of evaporator fan performance without removing 
panels or creating air by-pass of the coils. Condensate pan 
shall be internally sloped and conform to ASHRAE 62-89 self-
draining standards. Condensate connection shall be a minimum 
of 3/4” I.D. female and be a ridged mount connection.

Indoor (Evaporator) Fan Assembly

The indoor fan shall be a factory installed belt drive assembly 
that includes an adjustable pitch motor pulley. Job site selected 
(B.H.P.) brake horsepower shall not exceed the motors 
nameplate horsepower rating, plus the service factor. Units 
shall be designed not to operate above service factor. Fan 
wheel shall be double-inlet type with forward-curved blades, 
dynamically balanced to operate smoothly throughout the entire 
range of operation. Airflow design shall be constant air volume. 
Bearings shall be sealed and permanently lubricated for longer 
life and no maintenance.

Outdoor (Condenser) Fan Assembly

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be 
dynamically balanced for smooth operation. The outdoor fan 
motor shall be totally enclosed with permanently lubricated 
bearings, internally protected against overload conditions and 
staged independently.

Refrigerant Components

Compressor:

a. Shall be internally protected with internal high-pressure 

relief and over temperature protection.

b. Shall have internal spring isolation and sound muffling to 

minimize vibration and noise, and be externally isolated 
on a dedicated, independent mounting.

Coils:

a. Evaporator and condenser coils shall have aluminum 

plate fins mechanically bonded to seamless internally 

http://www.rezine.net

Page 10

Summary of Contents for ZJ Series

Page 1: ...T2950 365 Days Thermostat CO2 Demand Control Ventilation BAS Networkable with free Web Software Freeze and Undervoltage protections High Low Pressure switch Smoke Detectors in both Supply and Return A...

Page 2: ...osion Coating www armorguardss316 com UVC lights for HVAC www steril aire usa com Quiet Efficient High CFM Air Handlers www miair com Boilers www raypak com 365 Days Various Thermostats www thermostat...

Page 3: ...completely charged wired piped and tested at the factory to provide a quick and easy field installation All models including those with an economizer are convertible between bottom and horizontal duct...

Page 4: ...iagrams 57 Component Location Gas Electric 3 4 PVC female condensate drain Knockout for side control entry GFCI convenience outlet Smoke detector Slide in economizer Economizer hood HACR breaker Belt...

Page 5: ...enience outlet Smoke detector Slide in economizer Economizer hood HACR breaker Belt drive blower High efficiency compressor Copper tube aluminum fin condensing coil Full perimeter baserails with forkl...

Page 6: ...s 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options SS Drain Pan Configuration Options not required for all u...

Page 7: ...LED Each high and low pressure switch alarm as well as each freezestat alarm has its own flash code The control board saves the five most recent alarms in memory and these alarms can be reviewed at a...

Page 8: ...e years of trouble free operation in corrosive environments Bottom Drain Connection An optional bottom drain connection is available for inside the curb connections for applications in cold environmen...

Page 9: ...the unit and the finished roof These full perimeter curbs meet the requirements of the National Roofing Contractors Association NRCA and are shipped knocked down for field assembly Roof curbs are desi...

Page 10: ...ll be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be CSA listed classified to ANSI Z21 47 UL 1995 CSA No 2...

Page 11: ...shall be of the inshot type constructed of aluminum coated steel and contain air mixture adjustments All gas piping shall enter the unit cabinet at a single location through either the side or curb w...

Page 12: ...all fully close on power loss Other Pre engineered Accessories Available Roof Curb 14 and 8 high full perimeter curb with wood nailer shipped knocked down Barometric Relief Damper Contains a rain hood...

Page 13: ...81 1 80 5 81 1 80 5 No burners 2 4 3 5 3 5 3 5 4 5 3 5 No stages 1 1 2 2 1 1 2 2 1 1 2 2 Temperature Rise Range F 15 45 40 70 35 70 55 90 25 55 45 75 25 70 45 70 25 55 35 65 35 70 45 75 Gas Limit Sett...

Page 14: ...tal CFM 4200 4200 4200 BELT DRIVE EVAP FAN DATA Quantity 1 1 1 Fan Size Inch 12 x 10 12 x 10 12 x 10 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VL40 1VL40 1VL40 Blower Sheave AK74 AK61 AK5...

Page 15: ...3 25 5 25 kW 3 34 17 F capacity rating MBH 19000 27000 35000 System power KW COP 2 60 kW 2 15 3 86 kW 2 06 4 76 kW 2 15 HSPF Btu Watts hr 7 70 7 70 7 70 DIMENSIONS inches Length 82 1 4 82 1 4 82 1 4...

Page 16: ...39 A36 A36 Motor HP each 1 1 2 1 1 2 1 1 2 RPM 1725 1725 1725 Frame size 56 56 56 FILTERS 15 x 20 x 1 or 2 2 2 2 14 x 25 x 1 or 2 1 1 1 ZJ XP036 060 Unit Limitations Size Tons Unit Voltage Unit Limita...

Page 17: ...3 20 3 47 4 2 6 36 4 30 5 24 6 18 8 67 46 3 2 3 46 3 39 4 33 4 27 4 21 5 43 0 2 6 43 0 37 7 31 8 26 0 20 1 62 42 8 2 3 42 8 42 8 42 2 36 3 30 3 24 3 39 5 2 6 39 5 39 5 39 3 33 4 27 5 21 6 57 42 4 2 3...

Page 18: ...3 17 3 12 3 62 29 6 3 6 29 6 29 6 29 4 24 4 19 5 14 5 27 0 3 9 27 0 27 0 27 0 22 7 17 8 12 8 57 28 9 3 5 28 9 28 9 29 7 24 7 19 7 14 7 26 3 3 9 26 3 26 3 26 3 22 3 17 4 12 4 1350 72 35 4 3 5 29 3 23...

Page 19: ...32 1 25 6 67 59 3 2 8 57 1 49 2 42 9 36 6 30 3 55 7 3 2 54 6 48 2 41 7 35 2 28 8 62 48 9 2 8 48 9 48 9 49 3 43 0 36 7 30 4 50 1 3 2 50 1 50 1 50 1 43 7 37 2 30 7 57 52 1 2 9 52 1 52 1 52 1 45 8 39 5...

Page 20: ...1 29 1 24 1 19 0 62 38 0 4 5 38 0 38 0 37 9 32 8 27 6 22 4 32 9 5 0 32 9 32 9 32 9 29 1 24 1 19 1 57 40 9 4 5 40 9 40 9 38 8 33 7 28 5 23 3 37 4 5 0 37 4 37 4 34 8 29 8 24 8 19 8 1800 72 46 2 4 6 35...

Page 21: ...39 0 30 9 67 75 0 3 7 72 4 63 1 54 9 46 8 38 6 69 1 4 3 67 8 59 7 51 6 43 6 35 5 62 69 3 3 7 69 3 69 3 69 3 61 2 53 0 44 9 63 4 4 2 63 4 63 4 63 4 55 3 47 2 39 1 57 67 6 3 7 67 6 67 6 67 6 59 5 51 3...

Page 22: ...5 33 1 26 8 20 5 62 44 1 6 0 44 1 44 1 44 1 37 6 31 2 24 7 38 9 6 6 38 9 38 9 38 9 33 4 27 1 20 8 57 46 3 6 0 46 3 46 3 46 3 39 9 33 4 27 0 42 1 6 7 42 1 42 1 42 1 35 8 29 5 23 1 2250 72 55 3 6 2 41 3...

Page 23: ...6 2 4 35 7 30 2 24 6 19 0 67 44 1 2 1 44 1 38 8 33 1 27 3 21 5 40 3 2 4 40 3 37 1 31 6 26 0 20 4 62 37 1 2 1 37 1 37 1 37 1 31 4 25 6 19 8 36 3 2 4 36 3 36 3 36 3 30 7 25 1 19 5 57 34 2 2 1 34 2 34 2...

Page 24: ...2 4 18 0 13 5 62 28 1 3 4 28 1 28 1 28 1 23 6 19 1 14 6 24 7 3 8 24 7 24 7 24 7 21 2 16 7 12 3 57 28 1 3 4 28 1 28 1 28 1 23 6 19 1 14 6 25 5 3 8 25 5 25 5 25 5 21 1 16 6 12 2 1350 72 33 0 3 4 28 5 23...

Page 25: ...31 3 24 1 67 57 2 2 8 57 2 51 1 43 6 36 1 28 5 52 5 3 2 52 5 48 4 41 1 33 9 26 7 62 51 4 2 8 51 4 51 4 51 4 43 9 36 4 28 8 46 6 3 2 46 6 46 6 46 6 39 4 32 1 24 9 57 51 7 2 8 51 7 51 7 51 7 44 2 36 7...

Page 26: ...3 28 5 22 7 16 9 62 35 8 4 5 35 8 35 8 35 8 29 8 23 9 18 0 32 3 4 9 32 3 32 3 32 3 26 9 21 1 15 3 57 35 8 4 4 35 8 35 8 35 8 29 9 24 0 18 1 32 9 4 9 32 9 32 9 32 9 27 1 21 3 15 5 1800 72 43 2 4 4 36...

Page 27: ...39 1 30 6 67 72 1 3 8 72 1 62 5 54 0 45 4 36 9 67 5 4 3 67 5 60 8 52 3 43 7 35 2 62 64 9 3 7 64 9 64 9 64 9 56 4 47 8 39 3 61 1 4 2 61 1 61 1 61 1 52 6 44 1 35 6 57 63 1 3 7 63 1 63 1 63 1 54 6 46 1...

Page 28: ...41 2 33 2 25 1 45 7 6 5 45 7 45 7 45 7 37 7 29 6 21 5 2500 72 58 7 6 0 52 3 43 5 34 8 26 0 54 0 6 6 51 2 42 3 33 4 24 5 67 53 2 5 9 53 2 53 2 47 3 38 5 29 8 48 3 6 5 48 3 48 3 45 6 36 8 27 9 62 49 8...

Page 29: ...00 55 MBH 18 9 25 7 32 5 39 4 46 2 53 0 59 9 66 7 KW 3 6 3 8 3 9 4 0 4 2 4 3 4 4 4 6 70 MBH 18 3 25 1 31 9 38 8 45 6 52 4 59 3 66 1 KW 4 6 4 7 4 8 5 0 5 1 5 2 5 4 5 5 80 MBH 18 3 25 1 31 9 38 7 45 6 5...

Page 30: ...3 0 83 962 806 0 86 1008 838 0 90 1052 871 0 93 2000 887 819 0 88 943 853 0 92 994 886 0 95 1040 918 0 98 1084 951 1 02 Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includ...

Page 31: ...104 1 18 1077 1150 1 23 1119 1194 1 28 1162 1234 1 32 2300 1034 1151 1 24 1075 1197 1 28 1116 1243 1 33 1158 1286 1 38 2400 1075 1250 1 34 1115 1296 1 39 1156 1341 1 44 2500 1118 1354 1 45 1158 1400 1...

Page 32: ...7 2200 996 1059 1 14 1036 1104 1 18 1077 1150 1 23 1119 1194 1 28 1162 1234 1 32 2300 1034 1151 1 24 1075 1197 1 28 1116 1243 1 33 1158 1286 1 38 2400 1075 1250 1 34 1115 1296 1 39 1156 1341 1 44 2500...

Page 33: ...6 0 83 953 818 0 88 1001 860 0 92 1045 901 0 97 1087 939 1 01 2000 936 857 0 92 990 899 0 96 1038 941 1 01 1082 981 1 05 Air Flow CFM Available External Static Pressure IWG1 1 Blower performance inclu...

Page 34: ...0 1017 1063 1 14 1056 1098 1 18 1098 1138 1 22 1141 1180 1 27 1186 1223 1 31 2300 1063 1151 1 23 1102 1186 1 27 1144 1226 1 31 1187 1268 1 36 2400 1111 1243 1 33 1151 1278 1 37 1192 1318 1 41 2500 116...

Page 35: ...1046 1030 1 11 1084 1075 1 15 1123 1121 1 20 1162 1168 1 25 1200 1215 1 30 2300 1082 1128 1 21 1121 1172 1 26 1160 1219 1 31 1198 1266 1 36 2400 1120 1231 1 32 1159 1276 1 37 1198 1322 1 42 2500 1159...

Page 36: ...8 0 97 1015 951 1 02 1057 992 1 06 1100 1027 1 10 2000 924 891 0 96 964 937 1 01 1005 982 1 05 1047 1026 1 10 1090 1066 1 14 1133 1102 1 18 Air Flow CFM Available External Static Pressure IWG1 1 Blowe...

Page 37: ...1 14 1036 1104 1 18 1077 1150 1 23 1119 1194 1 28 1162 1234 1 32 2300 1034 1151 1 24 1075 1197 1 28 1116 1243 1 33 1158 1286 1 38 2400 1075 1250 1 34 1115 1296 1 39 1156 1341 1 44 2500 1118 1354 1 45...

Page 38: ...167 1182 1 27 2200 996 1059 1 14 1036 1104 1 18 1077 1150 1 23 1119 1194 1 28 1162 1234 1 32 2300 1034 1151 1 24 1075 1197 1 28 1116 1243 1 33 1158 1286 1 38 2400 1075 1250 1 34 1115 1296 1 39 1156 13...

Page 39: ...863 0 93 977 903 0 97 1021 945 1 01 1066 988 1 06 1111 1029 1 10 2000 934 901 0 97 973 936 1 00 1015 976 1 05 1058 1018 1 09 1103 1061 1 14 1149 1102 1 18 Air Flow CFM Available External Static Press...

Page 40: ...180 1 27 2200 1017 1063 1 14 1056 1098 1 18 1098 1138 1 22 1141 1180 1 27 1186 1223 1 31 2300 1063 1151 1 23 1102 1186 1 27 1144 1226 1 31 1187 1268 1 36 2400 1111 1243 1 33 1151 1278 1 37 1192 1318 1...

Page 41: ...67 1 25 2200 1046 1030 1 11 1084 1075 1 15 1123 1121 1 20 1162 1168 1 25 1200 1215 1 30 2300 1082 1128 1 21 1121 1172 1 26 1160 1219 1 31 1198 1266 1 36 2400 1120 1231 1 32 1159 1276 1 37 1198 1322 1...

Page 42: ...14 0 11 0 07 0 09 1800 0 16 0 13 0 08 0 11 2000 0 18 0 15 0 10 0 13 2200 0 20 0 17 0 12 0 15 2400 0 23 0 20 0 14 0 17 2600 0 26 0 23 0 16 0 20 2800 0 29 0 26 0 19 0 23 3000 0 32 0 30 0 22 0 26 Altitud...

Page 43: ...odel Datum Dia in Bore in Model 036 3 0 1 1 2 1725 0 8 1 15 56 2 4 3 4 5 8 1VL40 7 0 1 AK74 A39 1 1 2 1725 0 8 1 15 56 2 4 3 4 5 8 1VL40 5 7 1 AK61 A36 048 4 0 1 1 2 1725 0 8 1 15 56 2 4 3 4 5 8 1VL40...

Page 44: ...on to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level ratings Octave Band Centerline Frequency Hz RPM BHP 63 125 250 500 1000 2000 4000 8000...

Page 45: ...3 60 6 4 45 0 10 0 1 3 2 6 0 0 None 11 9 15 E07 6 8 8 13 5 15 E10 10 1 12 18 4 20 E15 13 6 16 23 7 25 E20 19 5 23 32 6 35 575 3 60 5 4 38 0 8 5 1 3 2 0 0 0 None 9 8 15 E10 10 6 10 15 2 20 E15 15 9 15...

Page 46: ...83 5 90 230 3 60 17 3 123 0 27 5 2 3 5 2 0 0 None 29 5 40 E05 5 3 12 7 29 5 40 E07 7 5 18 0 29 5 40 E10 10 6 25 5 38 4 45 E15 15 9 38 2 54 3 60 E20 21 2 51 0 70 2 80 E30 29 6 71 2 95 5 100 460 3 60 9...

Page 47: ...0 0 None 11 4 15 E07 6 8 8 21 6 25 E10 10 1 12 26 6 30 E15 13 6 16 31 8 35 E20 19 5 23 40 7 45 575 3 60 5 4 38 0 8 5 0 6 2 0 0 0 None 9 2 15 E10 10 6 10 22 0 25 E15 15 9 15 28 4 30 E20 21 2 20 34 7 3...

Page 48: ...6 104 0 110 230 3 60 17 3 123 0 27 5 2 3 5 2 0 0 None 27 0 35 E05 5 3 12 7 42 9 50 E07 7 5 18 0 49 6 60 E10 10 6 25 5 58 9 60 E15 15 9 38 2 74 8 80 E20 21 2 51 0 90 7 100 E30 29 6 71 2 116 0 125 460 3...

Page 49: ...5 0 10 0 1 3 2 6 5 0 None 16 9 20 E07 6 8 8 19 7 20 E10 10 1 12 24 7 25 E15 13 6 16 29 9 30 E20 19 5 23 38 8 40 575 3 60 5 4 38 0 8 5 1 3 2 0 4 0 None 13 8 15 E10 10 6 10 20 2 25 E15 15 9 15 26 6 30 E...

Page 50: ...6 96 0 100 230 3 60 17 3 123 0 27 5 2 3 5 2 10 0 None 39 5 50 E05 5 3 12 7 39 5 50 E07 7 5 18 0 41 6 50 E10 10 6 25 5 50 9 60 E15 15 9 38 2 66 8 70 E20 21 2 51 0 82 7 90 E30 29 6 71 2 108 0 110 460 3...

Page 51: ...0 None 16 4 20 E07 6 8 8 26 6 30 E10 10 1 12 31 6 35 E15 13 6 16 36 8 40 E20 19 5 23 45 7 50 575 3 60 5 4 38 0 8 5 0 6 2 0 4 0 None 13 2 15 E10 10 6 10 26 0 30 E15 15 9 15 32 4 35 E20 21 2 20 38 7 40...

Page 52: ...61 6 114 0 125 230 3 60 17 3 123 0 27 5 2 3 5 2 10 0 None 37 0 45 E05 5 3 12 7 52 9 60 E07 7 5 18 0 59 6 70 E10 10 6 25 5 68 9 70 E15 15 9 38 2 84 8 90 E20 21 2 51 0 100 7 110 E30 29 6 71 2 126 0 150...

Page 53: ...MOSTAT SWITCHES TO THE SET BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER 1ELECTRO...

Page 54: ...88 84 105 109 113 X Y LEFT FRONT XP036 060 Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F 036 3 0 580 575 39 20 1...

Page 55: ...Unitary Products Group 53 ZJ036 060 Unit Dimensions ZJ036 060 Cooling Only Electric Heat Front View XP036 060 Heat Pump Electric Heat Front View ZJ036 060 Cooling Only Gas Heat Front View http www re...

Page 56: ...rized Damper Rain Hood ZJ XP036 060 Rear View Detail A 27 1 2 27 1 2 1 5 8 19 1 2 44 7 8 19 3 4 Rear View Detail B Dimension A Fixed Outdoor Air Damper 12 16 1 2 Motorized Damper LH End View 27 1 2 27...

Page 57: ...nit can be located by the slice in the insulation Control Wiring2 2 Do not remove the 2 knockout ring Side Bottom B 2 KO1 Power Wiring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bot...

Page 58: ...251933 YTG B 0806 56 Unitary Products Group ZJ XP036 060 Typical Applications http www rezine net Page 58...

Page 59: ...http www rezine net Page 59...

Page 60: ...http www rezine net Page 60...

Page 61: ...temperature supply air temperature small space cooling demand and large space cooling demand Outside Air CO2 Sensor to close the economizer if CO2 is present Inside Demand Ventilation using one CO2 se...

Page 62: ...http www rezine net Page 62...

Page 63: ...is allows you to apply this control package to equipment provided by a variety of suppliers or to equipment that has already been installed This flexibility makes the Facility Explorer Commercial Zoni...

Page 64: ...has not yet been installed COMMERCIAL ZONING PACKAGE Bypass Damper and Actuator Assembly A round or rectangular bypass damper is combined with an M910xHGA non spring return actuator FX16 Master Contr...

Page 65: ...http www rezine net Page 65...

Page 66: ...l is a digital controller from the VAV Modular Assembly VMA Series or the LN Series Each model in the VMA1400 Series and the LN Series combines a controller pressure sensor and actuator housed in one...

Page 67: ...tion 3 4 or 1 fiberglass insulation Scrim reinforced foil faced insulation meeting American Society for Testing and Materials ASTM C1136 for mold mildew and humidity resistance 1 2 Elastomeric closed...

Page 68: ...gnal to the controller enabling it to quietly and precisely measure airflow Bundled with the TSL Terminal is a digital controller from the VAV Modular Assembly VMA Series or the LN Series Each model i...

Page 69: ...ETL listed as an assembly for safety compliance Automatic reset primary and back up secondary thermal limits Primary auto reset high limit Secondary high limit Airflow switch Single point power connec...

Page 70: ...11 1 4 12 800 1200 30 16 x 15 x 13 6 1 2 11 7 8 14 3 4 13 3 4 14 1100 1800 38 20 x 17 5 x 17 5 6 1 2 13 7 8 18 3 4 16 1 4 16 1500 2200 42 24 x 17 5 x 17 5 6 1 2 15 7 8 22 3 4 16 1 4 22 3000 5400 72 34...

Page 71: ...zes 6 and 8 refer to the Single Duct Variable Air Volume Terminal Model TSS All dimensions are in inches with a tolerance of 1 8 Weights are in pounds Weights are for the basic unit with the indicated...

Page 72: ...http www rezine net Page 72...

Page 73: ...ts Applications Steril Aire s multi patented UVC Emitter provides the best and longest lasting UVC performance available As shown in the comparison graph above it has been independently tested to deli...

Page 74: ...streams of 35 170 F 100 RH and at up to 2000 fpm velocity The design shall include RF and EMI suppression T Th he e s so oc ck ke et t shall be a Circline 4 pin type with sufficient wire length to fac...

Page 75: ...http www rezine net Page 75...

Page 76: ...http www rezine net Page 76...

Page 77: ...http www rezine net Page 77...

Page 78: ...http www rezine net Page 78...

Reviews: