251933-YTG-B-0806
40
Unitary Products Group
Additional Static Resistance
Size
(Tons)
CFM
Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance
Tables.
Economizer
2 3
2. Deduct these values from the available external static pressure shown in the respective
Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100%
return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver
less CFM during full economizer operation.
Electric Heat kW
2
7 - 15
20 - 30
036 (3.0)
048 (4.0)
060 (5.0)
1000
0.08
0.07
0.04
0.06
1200
0.10
0.08
0.05
0.07
1400
0.12
0.09
0.06
0.08
1600
0.14
0.11
0.07
0.09
1800
0.16
0.13
0.08
0.11
2000
0.18
0.15
0.10
0.13
2200
0.20
0.17
0.12
0.15
2400
0.23
0.20
0.14
0.17
2600
0.26
0.23
0.16
0.20
2800
0.29
0.26
0.19
0.23
3000
0.32
0.30
0.22
0.26
Altitude/Temperature Correction Factors
Air
Temp.
Altitude (Ft.)
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
40
1.060
1.022
0.986
0.950
0.916
0.882
0.849
0.818
0.788
0.758
0.729
50
1.039
1.002
0.966
0.931
0.898
0.864
0.832
0.802
0.772
0.743
0.715
60
1.019
0.982
0.948
0.913
0.880
0.848
0.816
0.787
0.757
0.729
0.701
70
1.000
0.964
0.930
0.896
0.864
0.832
0.801
0.772
0.743
0.715
0.688
80
0.982
0.947
0.913
0.880
0.848
0.817
0.787
0.758
0.730
0.702
0.676
90
0.964
0.929
0.897
0.864
0.833
0.802
0.772
0.744
0.716
0.689
0.663
100
0.946
0.912
0.880
0.848
0.817
0.787
0.758
0.730
0.703
0.676
0.651
$LU7HPSHUDWXUH)
&RUUHFWLRQ)DFWRU
6HD/HYHO
IW
IW
IW
IW
IW
IW
IW
IW
IW
IW
http://www.rezine.net
Page 42
Summary of Contents for ZJ Series
Page 59: ...http www rezine net Page 59...
Page 60: ...http www rezine net Page 60...
Page 62: ...http www rezine net Page 62...
Page 65: ...http www rezine net Page 65...
Page 72: ...http www rezine net Page 72...
Page 75: ...http www rezine net Page 75...
Page 76: ...http www rezine net Page 76...
Page 77: ...http www rezine net Page 77...
Page 78: ...http www rezine net Page 78...