Table 27: Additional Static Resistance ZF120/150 Cabinet (Imperial)
CFM
Cooling Only
1
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
3
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Perfor-
mance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of
the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Electric Heat KW
2
18
24
36
54
2300
0.08
0.02
0.08
0.09
0.10
0.13
2500
0.09
0.02
0.09
0.10
0.11
0.14
2700
0.11
0.03
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.53
0.56
0.59
0.65