5326602-XIM-B-1019
40
Johnson Controls Ducted Systems
ESP
(Pa)
Turns Open
0
1
2
3
4
5
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
m
3
/s
In
(kW)
Out
(kW)
87
2.63
4.01
3.21
2.53
3.55
2.84
2.44
3.20
2.56
2.36
2.88
2.31
2.23
2.51
2.01
2.05
2.15
1.72
149
2.54
3.84
3.07
2.43
3.38
2.70
2.33
3.02
2.42
2.23
2.70
2.16
2.10
2.35
1.88
1.91
1.99
1.59
199
2.43
3.65
2.92
2.32
3.20
2.56
2.20
2.84
2.27
2.08
2.50
2.00
1.96
2.18
1.75
1.75
1.83
1.46
249
2.32
3.46
2.76
2.20
3.01
2.41
2.07
2.66
2.12
1.90
2.28
1.83
1.81
2.01
1.61
-
-
-
299
2.20
3.25
2.60
2.07
2.82
2.26
1.93
2.47
1.97
1.70
2.05
1.64
-
-
-
-
-
-
349
2.06
3.05
2.44
1.93
2.63
2.10
1.78
2.28
1.82
-
-
-
-
-
-
-
-
-
399
1.92
2.84
2.27
1.78
2.44
1.95
-
-
-
-
-
-
-
-
-
-
-
-
448
1.77
2.63
2.10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES FOR TABLES ON PAGES 31 THROUGH 38:
•
“Turns Open” refers to the setting of the variable pitch
motor sheave, where “0 Turns Open” is fully closed.
•
Blower performance includes dry coil and 2” (51mm) throw-
away filters.
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
•
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure of
the blower.
ZF150 (44 kW) Bottom Duct Metric