5188236-BIM-A-0316
28
Johnson Controls Unitary Products
-05
(5.0)
208-1-60 24.4 144.2
38
4.4
7.6
10
NONE
-
-
-
52.5
70
E05
4
1
19.2
52.5
70
E07
5.6
1
26.9
55.7
70
E10
8
1
38.5
70.1
80
E15
11.9
2
57.2
93.5
100
E20
15.9
2
76.4
117.6
125
E30
22.2
2
106.7
155.4
175
230-1-60 24.4 144.2
38
4.4
7.6
10
NONE
-
-
-
52.5
70
E05
5.3
1
22.1
52.5
70
E07
7.5
1
31.2
61.1
70
E10
10.6
1
44.2
77.2
80
E15
15.9
2
66.2
104.8
110
E20
21.2
2
88.3
132.4
150
E30
29.6
2
123.3
176.2
200
208-3-60
16
110
24.9
4.4
7.6
10
NONE
-
-
-
42
50
E05
4
1
11.1
42
50
E07
5.6
1
15.5
42
50
E10
8
1
22.2
49.8
50
E15
11.9
2
33
63.3
70
E20
15.9
2
44.1
77.2
80
E30
22.2
2
61.6
99
100
230-3-60
16
110
24.9
4.4
7.6
10
NONE
-
-
-
42
50
E05
5.3
1
12.7
42
50
E07
7.5
1
18
44.6
50
E10
10.6
1
25.5
53.9
60
E15
15.9
2
38.2
69.8
70
E20
21.2
2
51
85.7
90
E30
29.6
2
71.2
111
125
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZD-03 Thru -05 - With Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps