5188236-BIM-A-0316
46
Johnson Controls Unitary Products
ZD-03 Thru -05 (3-5 Ton Direct Drive) Side Duct
UNIT
TONNAGE
MOTOR
1
SPEED
1. Factory set on medium speed tap.
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
3
3
3. Side Duct application (230 Volts)
5 (HI)
1574
320
1530
335
1488
349
1451
363
1411
376
1374
390
1331
403
1292
417
1249
430
4 (MED/HI)
1480
263
1433
276
1389
290
1347
303
1303
316
1257
329
1208
343
1153
358
1080
374
3 (MED)
1332
208
1286
221
1241
234
1195
246
1146
258
1097
272
1031
288
962
303
919
313
2 (MED/LOW)
1227
171
1178
183
1129
195
1076
207
1021
220
953
235
891
248
-
-
-
-
1 (LOW)
1075
130
992
134
930
145
858
158
-
-
-
-
-
-
-
-
-
-
4
3
5 (HI)
-
-
2067
696
2027
714
1991
734
1953
749
1910
764
1860
769
1770
743
1621
685
4 (MED/HI)
1913
539
1877
557
1839
571
1798
585
1764
602
1721
619
1677
638
1621
653
1545
639
3 (MED)
1722
408
1682
426
1634
438
1597
455
1554
472
1506
490
1450
505
1404
521
1370
536
2 (MED/LOW)
1475
321
1435
335
1388
352
1359
362
1319
376
1271
393
1220
411
1186
422
1142
437
1 (LOW)
1332
223
1290
237
1232
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
5 (HI)
2245
883
2247
931
2236
950
2211
964
2171
979
2114
971
2034
940
1948
898
1855
854
4 (MED/HI)
2135
771
2116
784
2108
808
2078
826
2041
844
2004
859
1955
861
1886
843
1792
806
3 (MED)
2010
637
1989
656
1975
675
1938
696
1900
715
1867
730
1822
740
1784
756
1716
748
2 (MED/LOW)
1672
408
1633
426
1586
438
1550
455
1509
472
1462
490
1408
505
1363
521
1330
536
1 (LOW)
1562
327
1529
339
1491
356
-
-
-
-
-
-
-
-
-
-
-
-