SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
71
Form 201.28-NM1.1
Issue date: 08/06/2021
5
Table 7 -
Optional one-pass evaporator (cont'd)
All dimensions - in. (mm)
YVAA
A,B
C
D
E-nozzle size Water volume gal
(L)
Minimum chilled
water flow rate
GPM (L/S)
Maximum chilled
water flow rate
GPM (L/S)
Frame
C
ond
.
23
3
20.8
(528)
73.2
(1859)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
24
5
21
(533)
92.9
(2360)
56.1
(1425)
8
71
(269)
590
(37)
2190
(138)
24
8
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
26
3
21
(533)
117.1
(2974)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
27
0
21
(533)
16.8
(427) 51.9 (1318)
8
82
(310)
590
(37)
2190
(138)
27
3
21
(533)
42.9
(1090)
70
(1778)
8
82
(310)
590
(37)
2190
(138)
27
5
22.5
(572)
44.7
(1135)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
27
8
22.5
(572)
88.3
(2243)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
29
5
22.5
(572)
88.6
(2250)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
30
3
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
Note
: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permittted. Glycol limits are higher. Contact your Johnson Controls Sales Office for ratings and further information.