JOHNSON CONTROLS
36
SECTION 4 - INSTALLATION
Form 201.28-NM1.1
Issue date: 08/06/2021
Recommended minimum clearances
Recommended clearances for the YVAA units are:
• Side to wall – 6 ft (1.8 m)
• Rear to wall – 6 ft (1.8 m)
• Control panel end to wall – 4 ft (1.2 m)
• Top – no obstructions whatsoever
• Distance between adjacent units – 10 ft (3 m)
Figure 5 -
Acceptable minimum clearances around
and between units
1.8 m (6
ft)
Minimum
1.2 m (4 ft)
Minimum
3 m (10
ft)
Minimum
Control panel
C
A
A
Tube Removal
Clearance Area
Tube Removal
Clearance Area
B
Clearance dimensions provided in
are necessary to maintain good
airflow and ensure correct unit opera
-
tion. It is also necessary to consider ac-
cess requirements for safe operation and
maintenance of the unit and power and
control panels. Local health and safety
regulations, or practical considerations
for service replacement of large compo-
nents, may require larger clearances than
those recommended.
Table 2 -
Minimum evaporator tube removal clearance
Model YVAA
Tube removal
clearance dimensions
A
B
C
Frame Cond Evap in. mm in. mm in. mm
015
3
B
26 663 36 914 132 3353
016
5
B
26 663 36 914 132 3353
017
8
C
26 663 36 914 156 3962
018
3
A
26 663 36 914 144 3658
019
5
A
26 663 36 914 144 3658
019
8
B
26 663 36 914 144 3658
020
0
C
26 663 36 914 156 3962
021
3
A
26 663 36 914 156 3962
021
5
C
26 663 36 914 156 3962
021
8
C
26 663 36 914 156 3962
023
3
B
26 663 36 914 132 3353
024
5
C
26 663 36 914 156 3962
024
8
C
26 663 36 914 156 3962
026
3
B
26 663 36 914 132 3353
027
0
D
26 663 36 914 192 4877
027
3
D
26 663 36 914 192 4877
027
5
E
26 663 36 914 192 4877
027
8
E
26 663 36 914 192 4877
029
5
E
26 663 36 914 192 4877
030
3
C
26 663 36 914 156 3962
030
5
E
26 663 36 914 156 3962
030
8
E
26 663 36 914 156 3962
031
8
E
26 663 36 914 192 4877
032
3
E
26 663 36 914 192 4877
033
3
C
26 663 36 914 156 3962
034
3
E
26 663 36 914 192 4877
034
5
E
26 663 36 914 192 4877
036
8
J
26 663 36 914 192 4877
037
3
F
26 663 36 914 144 3658
037
5
J
26 663 36 914 192 4877
039
8
J
26 663 36 914 192 4877
041
3
H
26 663 36 914 192 4877
042
5
H
26 663 36 914 144 3658
042
8
J
26 663 36 914 192 4877
044
3
G
26 663 36 914 144 3658
047
5
J
26 663 36 914 192 4877
048
3
G
26 663 36 914 144 3658
049
0
K
26 663 36 914 192 4877
050
0
J
26 663 36 914 192 4877
052
3
J
26 663 36 914 192 4877