SECTION 2 - ALL UNITS
FORM 145.05-SU3 (611)
ISSUE DATE 6/01/2011
JOHNSON CONTROLS
7
SECTION 2 - ALL UNITS
ON / OFF - MANUAL SWITCH
To turn the unit ON turn the ON/AUTO/OFF toggle
switch, located below the User Interface, from the
OFF to ON position.
Field Wiring
None Required.
Programming
PROGRAM KEY - Unit Data Subsection
• CLOCK SCHEDULE = USER DISABLED
ON / OFF - INTERNAL CLOCK
To turn the unit ON, turn the ON/AUTO/OFF toggle
switch, located below the User Interface, from the OFF
to AUTO position. The unit will then be switched to
ON based on the OCCUPIED schedule programmed
in the User Interface.
Field Wiring
None required.
Programming
PROGRAM KEY - Unit Data Subsection
• CLOCK SCHEDULE = USER ENABLED
ON / OFF - COMMUNICATED
To turn the unit ON turn the ON/AUTO/OFF toggle
switch, located below the User Interface, from the
OFF to AUTO position. The unit will then be switched
to ON based on a communicated OCCUPIED input.
Field Wiring
Connect the (+) wire of a shielded twisted pair to the
(+) terminal of the TB1 connector.
Connect the (-) wire of a shielded twisted pair to the (-)
terminal of the TB1 connector.
Programming
PROGRAM KEY - Unit Data Subsection.
• CLOCK SCHEDULE = USER DISABLED