York YSWU 10 Quick Start Up Manual Download Page 26

JOHNSON CONTROLS

26

FORM 145.05-SU3 (611) 

ISSUE DATE 6/01/2011

APPENDIX 2 - FACTORY RUN TEST PROCEDURE

Prompt Message #2

ROTATION CORRECT? – As the supply fan coasts 

down, you can open the door and verify proper rota-

tion. Press the check key if the rotation is correct. If 

not, identify why the rotation is wrong, and correct.
If both messages are accepted, PASS will be indicated 

at the display. Use the down arrow key to move to the 

next test.

COMPRESSOR SYSTEM TEST

(A, B, on all units; C and D on units 39 tons and great-

er; E and F on units 100 tons and greater).

To initiate the test press the check key (√ ). The control 

will ask you ARE YOU SURE? Press the check key 

(√ ) again.

Once underway, the controller will perform the fol-

lowing sequence:

1.  Set COMPRESSOR A to ON. 
2.  Wait 5 Seconds.
3.  Turn COMPRESSOR A to OFF.

Prompt Message #1

ROTATION CORRECT FOR 1A? – To verify proper 

rotation you need to attach a gauge set to the com-

pressor system prior to conducting the test. If rota-

tion is correct, the discharge pressure should increase 

rapidly. If the discharge and suction pressures remain 

the same, the rotation is not correct. Press the check 

key (√ ) if the compressor rotation is correct.

During this test sequence, the supply fan 

blower will operate at 50 hertz. Make sure 

this speed will not result in a static pres-

sure which could damage the building 

supply duct system.

Perform the following:

1.  Set the SUPPLY FAN to ON.
2.  Set SUPPLY FAN VFD AO to 60%.
3.  Wait 30 Seconds.
4.  Set COMPRESSOR A to ON.
5.  Wait 180 seconds.
6.  Set COMPRESSOR A to OFF.

7.  Wait 10 seconds.
8.  PASS will be indicated for this test and all outputs 

will be turned OFF.

If at any time during this test, the Com-

pressor System #1 status is not OKAY, all 

outputs will be immediately turned OFF 

and FAIL will be indicated for the test.

Repeat the above procedure for each of the compressor 

systems.

ANALOG OUTPUT OPERATION TEST

To initiate the test press the check key (√ ). The control 

will ask you ARE YOU SURE? Press the check key 

(√ ) again.

Once underway, the Unit Controller will perform the 

following sequence:

1.  Set OUTSIDE AIR / RETURN DAMPER to 

50%. 

2.  Set the CONDENSER WATER VALVE to 50%.
3.  Set the CONDENSER BYPASS VALVE (if pres-

ent) to 50%.

4.  Set the HOT WATER / STEAM VALVE (if pres-

ent) to 50%.

5.  Wait 45 seconds.

Prompt Message #1

ALL DAMPERS OPEN 50%? – Check the above ac-

tuators and verify they are approximately 50%. If they 

are press the ACCEPT - check key (√ ). 

If the actuators operated properly, use the down arrow 

key to move to the next test.

STAGED ELECTRIC HEAT TEST

This test can be run in one of two ways. The electri-

cal circuit could be checked without turning on the 

heaters by removing the fuses feeding the electric heat 

elements. Or if the fuses are left in place, the heater 

elements will be energized. If the heater elements are 

energized, the supply fan must be turned on or there is 

a possibility the limits will trip. The following proce-

dure will turn on the supply fan:

Summary of Contents for YSWU 10

Page 1: ...R COOLED SELF CONTAINED YSWU 10 105 TON INDOOR DOWNFLOW WATER COOLED SELF CONTAINED YSWD 10 105 TON WITH IPU2 CONTROL Issue Date June 01 2011 INDOOR PACKAGED AIR CONDITIONING UNITS QUICK START UP GUIDE NEW RELEASE Form 145 05 SU3 611 ...

Page 2: ...is individual will also be familiar with and com ply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to areas of potential hazard CAUTION identifies a hazard which could lead to damage to the machine damage to other equipment and or envi ronmental pollution Usually an in...

Page 3: ...ED SUPPLY AIR TEMPERATURE RESET COOLING 11 OUTDOOR AIR TEMPERATURE RESET COOLING 12 RETURN AIR TEMPERATURE RESET COOLING 13 SUPPLY FAN SPEED TEMPERATURE RESET COOLING 14 VAV HEATING 15 SECTION 5 FLEXSYS UNITS 17 FLEXSYS COOLING 17 FLEXSYS HEATING 18 CONDENSER WATER CONTROL 18 SECTON 6 OPTIONS 19 ECONOMIZER 19 VENTILATION 19 SUPPLY AIR TEMPERING 19 MORNING WARM UP 19 ADAPTIVE MORNING WARM UP 20 EME...

Page 4: ...d by contacting the nearest Johnson Con trols Service office NOMENCLATURE BASE MODEL NUMBER 1 2 3 4 U Upflow W Water Cooled S Self Contained Y YORK D Downflow for FlexSys 5 0 6 3 7 9 Base Product Type Nominal Tonnage It is the responsibility of operating service personnel to verify the applicability of these documents to the equipment in question If there is any question in the mind of operating s...

Page 5: ...re return air temperature or supply fan speed or FlexSys SECTION 1 INTRODUCTION Refer to applicable section for required field wiring miscellaneous connections and programming References to Programming indicates the setpoints that should be programmed verified under the respec tive key on the User Interface keypad SETPOINT PROGRAM OPTIONS DATE TIME and SCHED ULE keys Unit options should be program...

Page 6: ...JOHNSON CONTROLS 6 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 7: ...osition The unit will then be switched to ON based on the OCCUPIED schedule programmed in the User Interface Field Wiring None required Programming PROGRAM KEY Unit Data Subsection CLOCK SCHEDULE USER ENABLED ON OFF COMMUNICATED To turn the unit ON turn the ON AUTO OFF toggle switch located below the User Interface from the OFF to AUTO position The unit will then be switched to ON based on a commu...

Page 8: ...JOHNSON CONTROLS 8 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 9: ...NT 60 0 950 F Program Key Unit Data Subsection CONTROL METHOD WIRED ZONE TEMP Date Time Key Enter Correct Date and Time SECTION 3 CONSTANT VOLUME UNITS ZONE SENSOR CONTROL HEATING Field Wiring Connect zone sensor wiring to terminals 13 and 14 of terminal block CTB1 located inside the control panel see Appendix 1 CTB1 for zone sensor connections Miscellaneous Connections No additional connections r...

Page 10: ... Program key Unit Data Subsection CONTROL METHOD COMM ZONE TEMP Date Time Key Enter Correct Date and Time COMMUNICATED ZONE TEMP HEATING Field Wiring Hardwire BAS system to Primary Unit Controller Miscellaneous Connections No additional connections required Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 41 KW 17 KW 34 KW 68 KW Setpoints...

Page 11: ...in tons from the listed choices REFRIGERANT TYPE Select R22 407C or R410A COMP STAGING SEQ For units with four stages of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED...

Page 12: ...ng select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tra...

Page 13: ...ing select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tr...

Page 14: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Page 15: ...ensor tubing to the selected duct location A field supplied static pressure probe and tubing must be installed in the field prior to unit start up Refer to the unit IOM Form 145 05 NOM3 for details on how to install the static pressure probe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key ...

Page 16: ...JOHNSON CONTROLS 16 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 17: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Page 18: ...robe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key Heating Subsection HEATING SAT 80 0 115 00 F UNOCC ZONE HEATING SETPOINT 45 0 99 00 F HEAT LIMITTEMPERATURE 100 0 150 00 F RAT HEATING SETPOINT 550 F RAT COOLING SETPOINT 2 00 F Program Key Heating Subsection HEATING SYSTEM USER ENABLED ...

Page 19: ...STANDARD Setpoints Key Ventilation Subsection OA Damper Minimum Position 0 100 OA Damper Maximum Position OA Damper Minimum Position 100 Program Key Ventilation Subsection VENTILATION SYSTEM USER ENABLED Only used on Constant Volume Units COMFORT VENTILATION USER EN ABLED USER DISABLED Only used on Constant Volume Units SUPPLY AIR TEMPERING Field Wiring No additional connections required Miscellan...

Page 20: ...r to identify when an alarm is present connect the external device to terminals 15 and 16 of the TB1 terminal block Miscellaneous Connections No additional connections required Programming No programming is required PUMP OUTPUT Field Wiring The Primary Unit Controller has the ability to close three sets of dry contacts which can be used to ener gize the condenser water control pump To use this fea...

Page 21: ...TPOINTS PROGRAM or OPTIONS key will take the user to the Login Prompt When the user is first presented with the Login Prompt the pass word field will be blank If the user wishes to change Level 1 or Level 2 parameters the user must know the appropriate password At that point only the parame ters changeable under the specific password level will be displayed For example if the user presses the OP T...

Page 22: ...n at the digit to be changed After the desired numeric value has been entered press the key to save the new value and exit the edit mode Press ing the key will fill in the default value Edits will only be accepted when followed by pressing the key Pressing the key while in the edit mode will cancel the edit mode and leave the value unchanged If an out of range value is entered the Default High and...

Page 23: ...er the COMPRESSOR SYSTEMS key pressing the key will scroll sideways to the Sys 2 Pressures display and pressing the key will scroll sideways to the Sys Pressures display for the last system on the unit When programming numeric or non numeric values the key and the key are used to scroll forward down and backward up through the items to be pro grammed or set FORM 145 05 SU3 611 ISSUE DATE 6 01 2011...

Page 24: ...own Closed Run Closed Occupied Open Unoccupied Contacts Close When VAV Boxes Should Open 17 18 XX 13 14 15 16 9 10 LD13325A Wiring Notes 1 Wiring shown indicates typical wiring Refer to the IOM for more detailed wiring methods and options 2 All wiring is Class 2 low voltage 3 Maximum power available from the 24VAC terminal is 40 VA 4 Use shielded wire where shown 5 Relay contacts suitable for pilo...

Page 25: ...test shown has ended and was not successful APPENDIX 2 FACTORY RUN TEST PROCEDURE To start the test turn the UNIT rocker switch to the OFF position Press the SERVICE key and enter pass word 9725 See Section 6 of the IOM for information on how to enter the PASSWORD Use the down arrow key to scroll down to FACTO RY RUN TEST Press the check key and use the right arrow key to change from USER DISABLED...

Page 26: ...erform the following 1 Set the SUPPLY FAN to ON 2 Set SUPPLY FAN VFD AO to 60 3 Wait 30 Seconds 4 Set COMPRESSOR A to ON 5 Wait 180 seconds 6 Set COMPRESSOR A to OFF 7 Wait 10 seconds 8 PASS will be indicated for this test and all outputs will be turned OFF If at any time during this test the Com pressor System 1 status is not OKAY all outputs will be immediately turned OFF and FAIL will be indica...

Page 27: ...esent at the HEAT STAGE 1 heater ele ment If operating properly press the check key to accept If contactor and or heater element did not come on determine why and correct the problem If an accept is not received in 60 seconds the screen will indicate FAIL and all outputs will be homed Once accepted perform the following 1 Se t HEAT STAGE 1 output to OFF 2 Set HEAT STAGE 2 output to ON Prompt Messa...

Page 28: ...w york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2011 ALL RIGHTS RESERVED Form 145 05 SU3 611 Issue Date June 01 2011 Supersedes Nothing ...

Reviews: