York YSWU 10 Quick Start Up Manual Download Page 22

The password is entered by pressing the correct se-

quence of numerical keys (the 0 key through the 9 

key), then pressing the 

 key. As digits are entered, 

asterisks will be placed in the password field. Once 

entered, the menu system will compare the password 

to a list of stored passwords. If the entered password 

matches one of the stored passwords, the user is al-

lowed access at the specified level, and the display will 

show the first applicable parameter of the menu list, 

with the appropriate edit prompts. If the password is 

not correct, the screen will display “Password Incor-

rect” for two seconds and then revert back to the Login 

Prompt. Pressing the 

 key during password entry 

will cancel the password entry process and take the 

user back to the Login Prompt. 
Once a password has been accepted, reentry of that 

password will not be required until key activity is idle 

for fifteen minutes. This ensures that the menu system 

reverts to password protection within an acceptable 

timeout.

NAVIGATION

The keypad allows complete control of the system 

from a central location. The keypad offers a multitude 

of commands available to access displays, program 

parameters, and initiate system commands. The key-

pad consists of thirty-six keys, which are divided into 

three categories, Data Entry, Navigation and Menu Se-

lection keys. A description of each of the keys is con-

tained below.

Data Entry Keys

The Data Entry Keys provide a means to enter val-

ues for items that support edits. The keys available to 

support numeric input are the 0 through 9 keys, the 

decimal key, the +/- key, the 

 key and the 

 key. The 

keys available to support choice input are the 

 key, 

the 

 key, the 

 key, and the 

 key. 

Once editing has 

started, the user must press either the

 

 

key or the

 

 

key

. Any other key press will result in the “

Press 

 or 

 

to Exit

” message displayed for two seconds. If you 

try to edit an item that is view only, it will be ignored 

by the menu system.
When a numeric value that can be modified is dis-

played under the “Setpoints” menu key, the Default, 

High, and Low prompt will be shown in the upper right 

portion of the display. Pressing the +/- key, the decimal 

key, or any of the 0 through 9 keys will activate the 

edit mode and a request for the proper password will 

be made. After the proper password is entered, the cur-

sor will be shown at the digit to be changed. After the 

desired numeric value has been entered, press the 

 

key to save the new value and exit the edit mode. Press-

ing the 

 key will fill in the default value. Edits will 

only be accepted when followed by pressing the 

 

key. 

Pressing the 

 key while in the edit mode will cancel 

the edit mode and leave the value unchanged. If an out 

of range value is entered, the Default, High and Low 

prompt is replaced by the “Out of Range” message for 

two seconds.
When a choice value that can be modified is displayed 

under the “Program” or “Options” menu key, the 

 

 

prompt will be shown to the left of the present choice. 

The 

 key or the 

 key will allow the different choic-

es to be viewed, and pressing either one will activate 

the edit mode and a request for the proper password 

will be made. 

See Password section of this manual for 

the proper procedure for entering the password. 

When 

the desired choice is displayed, press the 

 

key to save 

the new value and exit the edit mode

Pressing the 

 

key while in the edit mode will cancel the edit mode 

and leave the value unchanged.

 Navigation Keys

The Navigation Keys provide a means to browse items 

within a menu. The keys currently available to support 

navigation are the Menu Select keys, the 

 key, the 

 

key, the 

 key, and the 

 key.

Pressing a Menu Select key brings the user to the first 

screen under that menu. The screens within each menu 

are arranged in a circular list. The user may browse 

through the screens using the 

 key and the 

 key. 

Pressing the 

 key will advance through the screens 

in order from top to bottom until the bottom screen has 

been reached. When the bottom screen is displayed, 

pressing the 

 key will wrap the display to the top 

screen of the menu. Pressing the 

 key will move 

through the screens in order from bottom to top until 

the top screen has been reached. When top screen is 

displayed, pressing the 

 key will wrap the display to 

the bottom screen of the menu. Once either the 

 key 

or the key 

 is pressed, pressing any Menu Select key 

will bring the user to the first screen under that menu 

(even if it is the same menu being viewed).
Navigation through the circular list of items can also be 

achieved by repeated presses of the same Menu Select 

key, as long as no other keys are pressed. For example, 

pressing the UNIT DATA key three times will bring 

the user to the third screen of the UNIT DATA menu; 

pressing the UNIT DATA key once, then pressing the 

JOHNSON CONTROLS

22

FORM 145.05-SU3 (611) 

ISSUE DATE 6/01/2011

APPENDIX 1 - USER INTERFACE 

Summary of Contents for YSWU 10

Page 1: ...R COOLED SELF CONTAINED YSWU 10 105 TON INDOOR DOWNFLOW WATER COOLED SELF CONTAINED YSWD 10 105 TON WITH IPU2 CONTROL Issue Date June 01 2011 INDOOR PACKAGED AIR CONDITIONING UNITS QUICK START UP GUIDE NEW RELEASE Form 145 05 SU3 611 ...

Page 2: ...is individual will also be familiar with and com ply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in this document to alert the reader to areas of potential hazard CAUTION identifies a hazard which could lead to damage to the machine damage to other equipment and or envi ronmental pollution Usually an in...

Page 3: ...ED SUPPLY AIR TEMPERATURE RESET COOLING 11 OUTDOOR AIR TEMPERATURE RESET COOLING 12 RETURN AIR TEMPERATURE RESET COOLING 13 SUPPLY FAN SPEED TEMPERATURE RESET COOLING 14 VAV HEATING 15 SECTION 5 FLEXSYS UNITS 17 FLEXSYS COOLING 17 FLEXSYS HEATING 18 CONDENSER WATER CONTROL 18 SECTON 6 OPTIONS 19 ECONOMIZER 19 VENTILATION 19 SUPPLY AIR TEMPERING 19 MORNING WARM UP 19 ADAPTIVE MORNING WARM UP 20 EME...

Page 4: ...d by contacting the nearest Johnson Con trols Service office NOMENCLATURE BASE MODEL NUMBER 1 2 3 4 U Upflow W Water Cooled S Self Contained Y YORK D Downflow for FlexSys 5 0 6 3 7 9 Base Product Type Nominal Tonnage It is the responsibility of operating service personnel to verify the applicability of these documents to the equipment in question If there is any question in the mind of operating s...

Page 5: ...re return air temperature or supply fan speed or FlexSys SECTION 1 INTRODUCTION Refer to applicable section for required field wiring miscellaneous connections and programming References to Programming indicates the setpoints that should be programmed verified under the respec tive key on the User Interface keypad SETPOINT PROGRAM OPTIONS DATE TIME and SCHED ULE keys Unit options should be program...

Page 6: ...JOHNSON CONTROLS 6 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 7: ...osition The unit will then be switched to ON based on the OCCUPIED schedule programmed in the User Interface Field Wiring None required Programming PROGRAM KEY Unit Data Subsection CLOCK SCHEDULE USER ENABLED ON OFF COMMUNICATED To turn the unit ON turn the ON AUTO OFF toggle switch located below the User Interface from the OFF to AUTO position The unit will then be switched to ON based on a commu...

Page 8: ...JOHNSON CONTROLS 8 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 9: ...NT 60 0 950 F Program Key Unit Data Subsection CONTROL METHOD WIRED ZONE TEMP Date Time Key Enter Correct Date and Time SECTION 3 CONSTANT VOLUME UNITS ZONE SENSOR CONTROL HEATING Field Wiring Connect zone sensor wiring to terminals 13 and 14 of terminal block CTB1 located inside the control panel see Appendix 1 CTB1 for zone sensor connections Miscellaneous Connections No additional connections r...

Page 10: ... Program key Unit Data Subsection CONTROL METHOD COMM ZONE TEMP Date Time Key Enter Correct Date and Time COMMUNICATED ZONE TEMP HEATING Field Wiring Hardwire BAS system to Primary Unit Controller Miscellaneous Connections No additional connections required Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 41 KW 17 KW 34 KW 68 KW Setpoints...

Page 11: ...in tons from the listed choices REFRIGERANT TYPE Select R22 407C or R410A COMP STAGING SEQ For units with four stages of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED...

Page 12: ...ng select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tra...

Page 13: ...ing select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct static tr...

Page 14: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Page 15: ...ensor tubing to the selected duct location A field supplied static pressure probe and tubing must be installed in the field prior to unit start up Refer to the unit IOM Form 145 05 NOM3 for details on how to install the static pressure probe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key ...

Page 16: ...JOHNSON CONTROLS 16 FORM 145 05 RP3 611 ISSUE DATE 6 01 2011 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 17: ... of cooling select SIMPLE for units with six stages of cooling select MIXED on four com pressor units only Options Key Supply System Subsection HIGH DUCT STATIC SW Should be set to INSTALLED if the optional High Duct Static Switch is installed SFVFD BYPASS Should be set to INSTALLED if the optional SF VFD Bypass is installed DUCT PRESS SENSOR 2 Should be set to IN STALLED if an optional 2nd duct s...

Page 18: ...robe and tubing Programming Options Key Heating Subsection HEATING SYS TYPE NONE ELECTRIC HOT WATER STEAM ELEC HEAT CAPACITY 11 KW 17 KW 34 KW 68 KW Setpoints Key Heating Subsection HEATING SAT 80 0 115 00 F UNOCC ZONE HEATING SETPOINT 45 0 99 00 F HEAT LIMITTEMPERATURE 100 0 150 00 F RAT HEATING SETPOINT 550 F RAT COOLING SETPOINT 2 00 F Program Key Heating Subsection HEATING SYSTEM USER ENABLED ...

Page 19: ...STANDARD Setpoints Key Ventilation Subsection OA Damper Minimum Position 0 100 OA Damper Maximum Position OA Damper Minimum Position 100 Program Key Ventilation Subsection VENTILATION SYSTEM USER ENABLED Only used on Constant Volume Units COMFORT VENTILATION USER EN ABLED USER DISABLED Only used on Constant Volume Units SUPPLY AIR TEMPERING Field Wiring No additional connections required Miscellan...

Page 20: ...r to identify when an alarm is present connect the external device to terminals 15 and 16 of the TB1 terminal block Miscellaneous Connections No additional connections required Programming No programming is required PUMP OUTPUT Field Wiring The Primary Unit Controller has the ability to close three sets of dry contacts which can be used to ener gize the condenser water control pump To use this fea...

Page 21: ...TPOINTS PROGRAM or OPTIONS key will take the user to the Login Prompt When the user is first presented with the Login Prompt the pass word field will be blank If the user wishes to change Level 1 or Level 2 parameters the user must know the appropriate password At that point only the parame ters changeable under the specific password level will be displayed For example if the user presses the OP T...

Page 22: ...n at the digit to be changed After the desired numeric value has been entered press the key to save the new value and exit the edit mode Press ing the key will fill in the default value Edits will only be accepted when followed by pressing the key Pressing the key while in the edit mode will cancel the edit mode and leave the value unchanged If an out of range value is entered the Default High and...

Page 23: ...er the COMPRESSOR SYSTEMS key pressing the key will scroll sideways to the Sys 2 Pressures display and pressing the key will scroll sideways to the Sys Pressures display for the last system on the unit When programming numeric or non numeric values the key and the key are used to scroll forward down and backward up through the items to be pro grammed or set FORM 145 05 SU3 611 ISSUE DATE 6 01 2011...

Page 24: ...own Closed Run Closed Occupied Open Unoccupied Contacts Close When VAV Boxes Should Open 17 18 XX 13 14 15 16 9 10 LD13325A Wiring Notes 1 Wiring shown indicates typical wiring Refer to the IOM for more detailed wiring methods and options 2 All wiring is Class 2 low voltage 3 Maximum power available from the 24VAC terminal is 40 VA 4 Use shielded wire where shown 5 Relay contacts suitable for pilo...

Page 25: ...test shown has ended and was not successful APPENDIX 2 FACTORY RUN TEST PROCEDURE To start the test turn the UNIT rocker switch to the OFF position Press the SERVICE key and enter pass word 9725 See Section 6 of the IOM for information on how to enter the PASSWORD Use the down arrow key to scroll down to FACTO RY RUN TEST Press the check key and use the right arrow key to change from USER DISABLED...

Page 26: ...erform the following 1 Set the SUPPLY FAN to ON 2 Set SUPPLY FAN VFD AO to 60 3 Wait 30 Seconds 4 Set COMPRESSOR A to ON 5 Wait 180 seconds 6 Set COMPRESSOR A to OFF 7 Wait 10 seconds 8 PASS will be indicated for this test and all outputs will be turned OFF If at any time during this test the Com pressor System 1 status is not OKAY all outputs will be immediately turned OFF and FAIL will be indica...

Page 27: ...esent at the HEAT STAGE 1 heater ele ment If operating properly press the check key to accept If contactor and or heater element did not come on determine why and correct the problem If an accept is not received in 60 seconds the screen will indicate FAIL and all outputs will be homed Once accepted perform the following 1 Se t HEAT STAGE 1 output to OFF 2 Set HEAT STAGE 2 output to ON Prompt Messa...

Page 28: ...w york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2011 ALL RIGHTS RESERVED Form 145 05 SU3 611 Issue Date June 01 2011 Supersedes Nothing ...

Reviews: