Installation &

Owner's man

ual

User' s Guide

INSTALLATION &
OWNER’S MANUAL

MINISPLIT FLOOR/CEILING
AIR CONDITIONER
MODELS : YOCC-YOHC 12-60

REQUIRED TOOLS

1.  Screw Driver  

  9.  Manifold Guage

2.   Hexagonal Wrench 

10.  Gas Leak Detector

3.   Torque Wrench  

11.  Vacuum Pump

4.   Spanner  

12.  Pipe Clamp

5.   Reamer  

13.  Pipe Cutter

6.   Hole Core Drill  

14.  Flare Tool Set

7.   Tape Measure  

15.  Electrical Circuit Tester

8.   Thermometer

EXTENDED PARTS

1.  Refrigerant Pipe : See Technical Speci

fi

 cation

2.  Pipe Insulation Material (Polyethylene foam 9 mm thick)
3.   Vinyl Tape
4.   Putty

•  Please read this installation manual carefully before starting installation
  of the unit.
•  This air conditioning system contains refrigerant under pressure, rotating
  parts and electrical connection which may be dangerous and can cause
  injury. Installation and maintenance of this air conditioning system should
  only be carried out by trained and quali

fi

 ed personnel.

•  After unpacking, please check the unit carefully for possible damage.
•  Before undertaking any work on the unit, make sure that the power supply
  has been disconnected.

CAUTIONS FOR INSTALLATION

•  Do not store or unpack the unit
  in a wet area or expose to rain
 or  

water.

It may cause the unit to short circuit and may
result electric shocks or

fi

 re.

•  Do not install in a place where
 

fl

 ammable gas may leak.

It may cause

fi

 re.

•  Do not conduct installation in wet
  area or in the rain.

It is a high risk to cause the electrical shocks.

•  This system is designed for
  domestic or residential use only.

If used in certain environments, such as a
manufacturing workplace, the equipment may
not function ef

fi

 ciently.

PART LIST

INDOOR UNIT

❥✱

 YOCC-YOHC

INSTALLATION ACCESSORIES

E N G L I S H

EN/FR

SAFETY PRECAUTIONS

035M00003-000

Description

Qty

USE

Hook

2

For wall mounting installation

Hanging arm

2

For ceiling

installation

Tapping Screw (ST2.9x10-C-H)

2

Remote Controller

1

Frame

Alkalina dry batteries (AM4)

1

Install & Owner’s manual and User’s
guide

2

Summary of Contents for YOCC-YOHC 12-60

Page 1: ...t by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power supply has been disconnected CAUTIONS FOR INSTALLATION Do not store or unpack the unit in a wet area or expose to rain or water It may cause the unit to short circuit and may result electric shocks or fire Do not install in a plac...

Page 2: ...cated to the air conditioner SYSTEM RELOCATION Relocating the air conditioner requires specialized knowledge and skills Please consult the shop where you bought the air conditioner if relocation is necessary for moving or remodelling Select a place which provides the space around the units as shown in the diagram below To prevent interference place at least 1m away Inverter type fluorescent lamp T...

Page 3: ...grille 2 Locate the hanging arm on the hanging screw bolt Refer to Chart 9 Prepare the mounting bolts on the unit Refer to Chart 10 3 Hang the unit on the hanging arm by sliding backward Securely tighten the mounting bolts on both sides Refer to Chart 9 Installation of the outdoor unit in a place exposed regularly to a strong wind Installation of the indoor unit in a place where there is an obstac...

Page 4: ...AL 5x2 0 3x2 0 3x2 0 2x2 0 3x2 0 2x2 0 WEAK ELECTRIC SIGNAL 1 core sheild wire 1x0 5mm2 2 core sheild wire 2x0 5mm2 TYPE 12000 18000 Btu h Cooling Only 24000 36000 Btu h Cooling Only 36000 60000 Btu h Cooling Only POWER PHASE 1 PHASE 1 PHASE 3 PHASE FREQUENCY AND VOLT 220 240V 50Hz 220 240V 50Hz 380V 3N 50Hz CIRCUIT BREAKER FUSE A 40 25 40 20 40 25 INDOOR UNIT POWER WIRING mm2 3x2 5 3x2 5 5x2 5 IN...

Page 5: ...le 3x2 5mm2 3 core cable 3x2 5mm2 OUTDOOR UNIT INDOOR UNIT POWER 220 240V 50Hz 3 core cable 3x2 5mm2 3 core cable 3x2 5mm2 OUTDOOR UNIT INDOOR UNIT POWER 220 240V 50Hz 1 core sheild wire 1x0 5mm2 3 core cable 3x2 5mm2 3 core cable 3x2 0mm2 OUTDOOR UNIT INDOOR UNIT POWER 220 240V 50Hz Chart 27 24000 36000 Btu h 1 PHASE Air Conditioner Link circuit For R 22 Cooling only 3 core cable 3x2 5mm2 3 core ...

Page 6: ...ge evacuate and recharge 2 Determine the cause and replace compressor 3 Remove charge evacuate and recharge 4 Replace it F Clicking sound is heard from the air conditioner In heating or cooling operation any plastic parts may expand or shrink due to a sudden temperature change in this event a clicking sound may occur In heating or cooling operation any plastic parts may expand or shrink due to a s...

Page 7: ...TION FUNCTION Auto Restart Function The unit will automatically restart after loss of the electrical power supply When power is restored the unit operation will restart according to all parameters set before the loss of power ANTI ICE and ANTI OVERHEAT This feature is used to prevent the indoor unit from freezing during cool or dry operation and overheating in heat mode During execution of anti ic...

Page 8: ...d Hi Med Low r min 1 190 1 000 890 1 280 1 190 1 000 1 280 1 190 1 000 1 310 1 200 1 000 1 310 1 200 1 000 1 310 1 200 1 000 1 310 1 200 1 000 820 695 620 820 695 620 Indoor coil Number of rows 2 3 3 3 3 3 3 3 3 Tube pitch a row pitch b mm 25 4 22 25 4 22 25 4 22 25 4 22 25 4 22 25 4 22 25 4 22 25 4 22 25 4 22 Fin spacing mm 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 Fin type Hydrophilic aluminum Tube ou...