INSTALLATION

FORM 115.20-NOM4 (105)

RECEIVING

Material in this shipment has been inspected at the 

factory and released to the transportation agency in 

good condition. When received, a visual inspection of 

all cartons should be made immediately. Any evidence 

of rough handling or apparent damage should be noted 

on the delivery receipt and the material inspected in 

the presence of the carrier’s representative.

STORAGE

If the equipment is not to be immediately installed, 

store it in a dry location with the motor protected 

against moisture, dust, corrosion and physical dam-

age.

DESCRIPTION

The YMB Series 2-pipe fan coil comes with a 4-row 

cooling / heating coil and a 120V multi-speed mo-

tor.

The YMBE Series 240V, 2-pipe fan coil comes with a 

4 row-cooling coil, 240V multi-speed motor, 240/24 

transformer, and up to 25kW of factory installed elec-

tric heat.  Models with more than 10kW also include a 

circuit breaker for branch circuit protection.  Control 

voltage is 24V.

The YMBE Series fan coil comes with a 4-row cool-

ing coil, 277V multi-speed motor, and up to 10kW of 

factory installed heat.  A unit mounted disconnect is 

standard.

The YMB-HW Series 4-pipe fan coil includes a 4 row 

cooling coil, a 2, 3, or 4 row heating coil installed in 

the reheat position, and a 120V multi-speed motor.  

If damage is found, a claim should be 

filed against the carrier immediately.

HORIZONTAL APPLICATION

These fan coil units are factory assembled for horizon-

tal left side down application without any modification 

required.  To convert to horizontal right side down, 

remove horizontal drain pan and A-coil assembly, flip 

horizontal drain pan over to right side and reinstall 

horizontal drain pan and A-coil into cabinet.  Secure 

forward  edge  of  horizontal  drain  pan  with  angle 

bracket.  The unit should be leveled in such a way 

that there is slope toward the condensate drain nipple 

to assure positive drainage.

WIRING

All wiring must comply with the local and national 

code requirements.  Units are provided with wiring 

diagrams and nameplate data to provide information 

required for necessary field wiring.  All wiring must 

comply with local and national code requirements.

YMBE SERIES

Fan  coil  units  with  10kW  or  less  electric  heat  are 

provided with a terminal block for connection of one 

electrical service.  Units with 15 kW and 20kW are 

provided with dual circuit breakers for the connection 

of two electrical services and units with 25kW are pro-

vided with three circuit breakers for the connection of 

three separate electrical services

 (see Figure 2 & 3).

These units may be provided with a class 2 transformer 

for 24-volt control circuits.  Should any add-on equip-

ment also have a class 2 transformer furnished, care 

must be taken to prevent interconnecting outputs of 

the two transformers by using a thermostat with iso-

lating contacts.

Any devices such as fan switches or 

thermostats that have been furnished 

by  the  factory  for  field  installation 

must  be  wired  in  strict  accordance 

with the wiring diagram that is sup-

plied with the unit. Failure to do so 

could result in damage or injury.

Summary of Contents for YMB

Page 1: ...nel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is only available in the YMBE series These units require a remote thermostat low voltage 4 wire thermostat MODELS YMB YMB HW YMBE YMB Series 2 pipe cooling and heating Replaces the MH S...

Page 2: ...e ordered through Publications Dept or downloaded http intranet york com web0003 library default asp MODEL WT MODEL WT MODEL WT 8YMB 115 8YMB HW 120 8YMBE 115 12YMB 120 10 12YMB HW 135 12YMBE 120 16 20YMB 210 16YMB HW 20YMB HW 210 264 16 20YMBE 210 TABLE 1 SHIPPING WEIGHTS LBS INSTALLATION 3 6 RECEIVING 3 STORAGE 3 DESCRIPTION 3 HORIZONTAL APPLICATION 3 WIRING 3 4 YMBE SERIES 3 PIPING 6 PIPING PRE...

Page 3: ...ed for horizon tal left side down application without any modification required To convert to horizontal right side down remove horizontal drain pan andA coil assembly flip horizontal drain pan over to right side and reinstall horizontal drain pan and A coil into cabinet Secure forward edge of horizontal drain pan with angle bracket The unit should be leveled in such a way that there is slope towa...

Page 4: ...RK INTERNATIONAL 4 FORM 115 20 NOM4 105 INSTALLATION FIG 2 YMBE WIRING CONNECTIONS 15 20 KW FIG 4 STANDARD LOW VOLTAGE WIRING FIG 5 T200 THERMOSTAT W CONTROLLER OPTION FIG 3 YMBE WIRING CONNECTIONS 25 KW ...

Page 5: ...motor 3 Vertical Horizontal drain pan right to left and left to right airflow 4 Manual air vent 5 Throw away filter MODEL A B C D E F G H FILTER SIZE 8YMB 8YMB HW 8YMBE 40 20 20 18 1 2 16 2 18 16 18 X 20 X 1 12YMB 10 12YMB HW 42 23 20 21 1 2 16 2 18 19 20 X 22 X 1 12YMBE 42 23 20 21 1 2 16 2 18 17 16 20YMB 16YMB HW 48 28 21 1 4 26 1 4 17 1 4 2 18 24 20 X 25 X 1 16 20YMBE 48 23 21 1 4 22 1 4 17 2 1...

Page 6: ...ms When all connections are complete the system must be pressure tested Repair any solder joint leaks and gently tighten any leaking valve packing nuts and piping accessories as required Hydronic systems are not designed to hold pressurized air and should only be tested with water TABLE 3 COIL CONNECTIONS COOLING COIL CONNECTIONS INCHES YMB YMBE YMB HW SIZES 8 10 12 7 8 ODS SIZES 16 20 1 1 8 ODS H...

Page 7: ...properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and exterior Make sure all ductwork is complete and available for full air flow Unit installed level to ensure proper drainage and operation Unit installed with proper clearances Ensure condensate ...

Page 8: ... 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2004 ALL RIGHTS RESERVED Form 115 20 NOM4 105 New Release Clean or Replace Air Filters Regu larly Dirty filters reduce the air and heat ing capacities of the Unit Ventilator When the filters are excessively dirty the unit heating capacity will be so re duced that it is ineffective for heating th...

Reviews: