background image

YORK INTERNATIONAL

6

FORM 115.20-NOM4 (105)

INSTALLATION

7

YORK INTERNATIONAL

FORM 115.20-NOM4 (105)

PIPING

The supply and return piping must be adequately sized 

to meet the design water flow requirements as specified 

for the specific installation 

(see table 3 for connection 

sizes).

  All chilled water piping must be insulated to 

prevent condensation.  It is also recommended that all 

piping be insulated to prevent freezing when piping is 

run in an unconditioned space.

PIPING PRECAUTIONS

•   Flush all piping prior to connection to remove 

all debris.

•   Use wet cotton rags to cool valve bodies when 

soldering.

•   Open  all  valves  (midway  for  hand  valves, 

manually open on motorized valves) prior to 

soldering.

•   When soldering to bronze or brass, heat the piping 

while in the socket/cup and begin introducing the 

solder when the flux boils rapidly.  Avoid direct 

flame into the solder joint.

•   Heat can only be applied to the cup of the valve 

body for a min i mal time before damage occurs 

(even with the use of wet rags.

•   Avoid rapid quenching of solder joints, as this 

will produce joints of inferior quality.

•  Connect  all  piping  per  accepted  industry 

standards and observe all regulations governing 

installation  of  piping  systems.    When  all 

connections are complete, the system must be 

pressure tested.  Repair any solder joint leaks and 

gently tighten any leaking valve packing nuts 

and piping accessories as required.  Hydronic 

systems are not designed to hold pressurized air 

and should only be tested with water.

TABLE 3 –  COIL CONNECTIONS 

COOLING COIL CONNECTIONS (INCHES)

YMB, YMBE, YMB-HW

SIZES 8, 10, 12

7/8" ODS

SIZES 16, 20

1-1/8" ODS

HEATING COIL CONNECTIONS (INCHES)

YMB-HW

SIZES 8, 10, 12, 16

7/8" ODS

SIZE 20

1-1/8" ODS

DRAIN PIPING

Condensate drain lines must be installed with adequate 

slope away from the unit to assure positive drain age.  

Since the drain pan is located on the suction side of 

the blower, a negative pressure exists at the drain pan 

and a minimum trap of 1-1/2 inches must be provided 

in the drain line to assure proper drainage.

Drain connections, primary and secondary, are 3/4" 

MPT.

When  connecting  piping  or  valve 

kits to fan coil units, do not bend or 

reposition the coil header tubing for 

alignment purposes.  This could cause 

a tubing fracture resulting in a water 

leak when water pressure is applied 

to the system.

Coil freeze protection is recommended 

for applications where the fan coil is 

located in ambient air locations (attics, 

crawl spaces, etc.) or within structures 

that may be unoccupied during freez-

ing conditions.  Consult the factory for 

additional information.

Summary of Contents for YMB

Page 1: ...nel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is only available in the YMBE series These units require a remote thermostat low voltage 4 wire thermostat MODELS YMB YMB HW YMBE YMB Series 2 pipe cooling and heating Replaces the MH S...

Page 2: ...e ordered through Publications Dept or downloaded http intranet york com web0003 library default asp MODEL WT MODEL WT MODEL WT 8YMB 115 8YMB HW 120 8YMBE 115 12YMB 120 10 12YMB HW 135 12YMBE 120 16 20YMB 210 16YMB HW 20YMB HW 210 264 16 20YMBE 210 TABLE 1 SHIPPING WEIGHTS LBS INSTALLATION 3 6 RECEIVING 3 STORAGE 3 DESCRIPTION 3 HORIZONTAL APPLICATION 3 WIRING 3 4 YMBE SERIES 3 PIPING 6 PIPING PRE...

Page 3: ...ed for horizon tal left side down application without any modification required To convert to horizontal right side down remove horizontal drain pan andA coil assembly flip horizontal drain pan over to right side and reinstall horizontal drain pan and A coil into cabinet Secure forward edge of horizontal drain pan with angle bracket The unit should be leveled in such a way that there is slope towa...

Page 4: ...RK INTERNATIONAL 4 FORM 115 20 NOM4 105 INSTALLATION FIG 2 YMBE WIRING CONNECTIONS 15 20 KW FIG 4 STANDARD LOW VOLTAGE WIRING FIG 5 T200 THERMOSTAT W CONTROLLER OPTION FIG 3 YMBE WIRING CONNECTIONS 25 KW ...

Page 5: ...motor 3 Vertical Horizontal drain pan right to left and left to right airflow 4 Manual air vent 5 Throw away filter MODEL A B C D E F G H FILTER SIZE 8YMB 8YMB HW 8YMBE 40 20 20 18 1 2 16 2 18 16 18 X 20 X 1 12YMB 10 12YMB HW 42 23 20 21 1 2 16 2 18 19 20 X 22 X 1 12YMBE 42 23 20 21 1 2 16 2 18 17 16 20YMB 16YMB HW 48 28 21 1 4 26 1 4 17 1 4 2 18 24 20 X 25 X 1 16 20YMBE 48 23 21 1 4 22 1 4 17 2 1...

Page 6: ...ms When all connections are complete the system must be pressure tested Repair any solder joint leaks and gently tighten any leaking valve packing nuts and piping accessories as required Hydronic systems are not designed to hold pressurized air and should only be tested with water TABLE 3 COIL CONNECTIONS COOLING COIL CONNECTIONS INCHES YMB YMBE YMB HW SIZES 8 10 12 7 8 ODS SIZES 16 20 1 1 8 ODS H...

Page 7: ...properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and exterior Make sure all ductwork is complete and available for full air flow Unit installed level to ensure proper drainage and operation Unit installed with proper clearances Ensure condensate ...

Page 8: ... 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2004 ALL RIGHTS RESERVED Form 115 20 NOM4 105 New Release Clean or Replace Air Filters Regu larly Dirty filters reduce the air and heat ing capacities of the Unit Ventilator When the filters are excessively dirty the unit heating capacity will be so re duced that it is ineffective for heating th...

Reviews: