
JOHNSON CONTROLS
164
FORM 150.72-NM3 (1020)
ISSUE DATE 10/05/2020
SECTION 7 – UNIT CONTROLS
Option 15 – Refrigerant Type:
R E F R I G E R A N T T Y P E
R – 4 1 0 A
Refrigerant type R-410A must be selected under Service
Mode. Refrigerant type is displayed under the OPTIONS
Key, but is only programmable in Service Mode.
Incorrect programming may cause
damage to compressors.
Option 16 – Expansion Valve Type:
E X P A N S I O N V A L V E T Y P E
T H E R M O S T A T I C
Expansion valve type, thermostatic or electronic
may be selected under Service Mode. Expansion valve
type is displayed under the OPTIONS key, but is
only programmable in Service Mode. YLAA chillers
will typically always be equipped with thermostatic
expansion valves.
Incorrect programming may cause
damage to compressors.
Also
see the UNIT KEYS PROGRAMMING QUICK
REFERENCE LIST in Table 15.
Option 17 – Flash Card Update:
F L A S H C A R D U P D A T E
D I S A B L E D
A Flash Card is used to input the operating program
into the chiller IPU. A Flash Card is used instead of an
EPROM. Normally, a Flash Card update is not required
and the message above will be displayed.
If the operating software is to be updated, insert the Flash
Card into the Flash Card input port. Turn off the unit
switch and set the Flash Card Update to “ENABLED”
using the ↑ and ↓ keys.
F L A S H C A R D U P D A T E
E N A B L E D
Press the ENTER key and the following message will
be displayed until the update has been completed. The
keypad and display will not respond during the update.
DO NOT reset or power down the chiller until the update
is completed.
F L A S H C A R D U P D A T I N G
P L E A S E W A I T . . .
After the update is completed, an automatic reboot will
occur. If an error occurred, the following message will
appear with the error code and no reboot will occur.
F L A S H C A R D U P D A T E
E R
R
O
R
XXXXX
If the update resulted in an error, the original program
will still be active. When an error occurs, assure the
correct Flash Card was utilized. Incorrect chiller
software will cause an error. If this is not the case, the
Flash Card is most likely defective or the IPU and I/O
combo board is bad.
Option 18 – Remote Temperature Reset:
R E M O T E T E M P R E S E T
I
N
P U T
XXXXXXXXXXXXXX
Remote Temp Reset input selection is programmable
according to the type of input utilized. The following
options are available:
• DISABLED (default)
• 0.0 – 10.0 (DC)
• 2.0 – 10.0V (DC)
• 0.0 – 20.0 mA
• 4.0 – 20.0 mA
The options display message for Re
-
mote Temp Reset Input only appears if
the Temp Reset Option is enabled un
-
der Service Mode. The option must be
enabled under the Service Mode for
the Remote Temperature Reset to oper
-
ate.
Summary of Contents for YLAA0195HE
Page 57: ...57 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 59: ...59 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 61: ...61 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 65: ...65 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 67: ...67 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 69: ...69 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 71: ...71 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 73: ...73 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 75: ...75 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 77: ...77 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 79: ...79 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 81: ...81 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 83: ...83 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 85: ...85 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 87: ...87 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 91: ...91 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 93: ...93 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 95: ...95 JOHNSON CONTROLS FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 SECTION 5 TECHNICAL DATA 5 5...
Page 204: ...JOHNSON CONTROLS 204 FORM 150 72 NM3 1020 ISSUE DATE 10 05 2020 NOTES...