5.2 Self-diagnosis
5.2.1 Indoor unit
No. Type
Contents
LED
Flashing
Remark
1
protection Over current protection of the
compressor occurs 4 times in 1h
Lamps of operation, timer,
defrosting (only fan ) flashing
simultaneously at 5Hz.
Whole unit is shut down.
It cannot recover unless
power is cut off
2
protection Outdoor protection (absent phrase,
phrase sequence and temperature
protection)
All lamps flashing at 5Hz
3
error
Room temperature sensor checking
channel is abnormal
Timer lamp flashing at 5Hz
4
error
Evaporator sensor checking channel is
abnormal
Operation lamp flashing at 5Hz
5
error
Condenser sensor checking channel is
abnormal
Defrosting lamp flashing at 5Hz
6
error
Temperature fuse is melt(reserved)
Operation lamp and timer lamp
flashing at 5Hz
Recover automatically
after errors are
eliminated(For T3
malfunction of 5HP,
can”t recover
automatically)
5.2.2 LEDs for the indication of outdoor trouble(3 phase type,3.5~5HP)
Type Contents
LED1
LED2
LED3
Trouble Phase
sequence
Flash
Off
Off
Trouble
Lack of phase
Flash
Off
Off
Trouble
Protection of pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Off
Flash
Trouble
Open-circuit and short-circuit trouble of T3
Off
Flash
Flash
Trouble
Open-circuit and short-circuit trouble of T4
Off
Flash
Off
Trouble
High temperature protection of condenser
Flash
Flash
Flash
Summary of Contents for YKHC 18
Page 24: ...22 Part8 Wiring diagram 1 YKHC 12 18 Indoor unit Outdoor unit...
Page 25: ...23 2 YKHC 24 Indoor unit Outdoor unit XT1 XT2 RT3 XS1 XP1 KM1 CAP1 FAN COMP CAP2 XT3 VALVE...
Page 35: ...33 4 Relocate the air in grid in the procedure of reversed order install the air in grid...
Page 40: ...38...
Page 45: ...43 Part12 Exploded view Indoor unit 1 YKHC 12 18...
Page 53: ...www johnsoncontrols com SM YKHC 18 48GB 03 07...